€160.50*
Please log in to receive your conditions.
Available, delivery time:
Login for addressed offer The entered number of pieces will be taken into account when creating the offer.
Product information "JUMO eTRON T100 zur Montage auf Hutschiene (1 Relaisausgang Wechsler 10A) "
JUMO eTRON T100 - electronic thermostat with timer function for mounting on 35 mm top-hat rails
Typ: 701052/8-02-31-00/000
- Version: Standard with factory settings
- Input: Thermocouple
- Power supply: DC 12 to 24 V +15/-15% / AC 230 V +10/-15%, 48 to 63 Hz
- Option: Digital output PhotoMOS ® relay (connection of resistance thermometers in three-wire circuit is not possible)
- Extra code: without
- Available in 5 different measuring groups
- Intuitive operation and configuration both directly on the device and via the setup programme using the USB interface
- User area with 8 adjustable parameters
- Data logger functionality for recording measurement data
- Dot matrix display with 64 x 80 pixels and support for 4 national languages
- Service and operating hours counter for monitoring device utilisation
- Connection via PCB terminals with push-in technology for easy installation
- Use of 10A relays (changeover contacts) for reliable switching
- Option for customer-specific linearisation of the measurement results in the setup program
- Limit value monitoring for precise control and monitoring of processes
- Timer function for time-controlled execution of actions
The digital thermostat measures the temperature using resistance thermometers, thermocouples or a current of 0(4) to 20 mA and can be configured as a simple heating or cooling thermostat depending on the selected mode.
The thermostat function (heating or cooling) can be started or limited in time using the timer function. The switching states of the relay and digital output, as well as the actual and setpoint values, are shown simultaneously on a backlit display with a resolution of 64 x 80 pixels. The display language can be switched between German, English, French and Spanish.
It is operated via four buttons on the front, while the electrical connection is made via print terminals with push-in technology.
PhotoMOS® relays for limit value monitoring or a digital input for connecting a potential-free contact can be added as an option. A setup programme is available for easy configuration.
Dimensions
Height | 3,1 cm |
---|---|
Length | 11 cm |
Width | 7,8 cm |
Weight
Weight | 200 g |
---|
Other attributes
Country of origin | DE |
---|---|
Customs tariff number | 90321020 |
Eingang | Thermoelement |
Spannungsversorgung | AC 230 V, +10/-15 %, 48 bis 63 Hz, DC 12 bis 24 V +15/-15% |
Downloads:
Analog Input
The following measurement input variants can be ordered.
Measurement input group 1 (resistance thermometer)
Designation Standard |
Measuring range |
Messgenauigkeita |
Ambient temperature influence |
ITS |
Pt100, Pt1000 in IEC 60751:2008 2-/3-Conductor circuit |
-200 to +600 °C |
£ 0,25 % |
£ 0,1´10 -3 1/K |
90 |
KTY 2X-6 in 2-Conductor circuit |
-50 to +150 °C |
£ 1% |
£ 0,1´10 -3 1/K |
- |
Customer Table |
150 W to 3000 W |
£ 0,25 % |
£ 0,1´10 -3 1/K |
- |
Measuring current |
ca. 0,5 mA |
Sensor Line Resistance |
≤ 30 W je Cable for 2- and 3-wire circuits |
Line Balancing |
Not required for 3-wire circuit. In the case of a 2-wire circuit, the line adjustment is carried out by software by entering a fixed line resistance. |
Particularities |
also programmable in °F |
a The accuracy specifications refer to the maximum measuring range. With smaller measuring spans, the linearization accuracy is reduced.
Measurement input group 2 (thermocouple)
Designation |
Norm |
Measuring range |
Messgenauigkeita |
Ambient Temperature Influence |
ITS |
Fe-CuNi “L” |
DIN 43710:1985-12 |
-200 to +900 °C |
±0,4 % |
£ 0,1´10 -3 1/K |
68 |
Fe-CuNi “J” |
DIN EN 60584-1:2014 |
-210 to +1200 °C |
±0,4 % ab -100 °C |
£ 0,1´10 -3 1/K |
90 |
NiCr-Ni “K” |
DIN EN 60584-1:2014 |
-270 to +1300 °C |
±0,4 % ab -80 °C |
£ 0,1´10 -3 1/K |
90 |
Customer Table |
-15 to 75 mV |
±0,4 % |
£ 0,1´10 -3 1/K |
- |
Measuring range start/end |
within the limits in 0.1 K increments |
Comparison Agent |
interne Messung über Pt1000 oder extern konstant 0 °C |
Reference Point Accuracy (Internal) |
±1 K |
Particularities |
also programmable in °F |
a The accuracy specifications refer to the maximum measuring range. With smaller measuring spans, the linearization accuracy is reduced.
b The ambient temperature influence is valid in the range of -20 to +55 °C.
Measurement input group 3 (unit signal)
Designation |
Measuring range |
Measurement accuracy |
Ambient temperature influence |
Strom (Spannungsabfall £ 2,5 V), frei skalierbar |
0 to 20 mA 4 to 20 mA |
£ 0,125 % |
£ 0,1´10 -3 1/K Abweichung von 22 °C |
Customer Table |
0 to 20 mA |
£ 0,125 % |
|
Particularities |
Skalierung einstellbar |
a The accuracy specifications refer to the maximum measuring range. With smaller measuring spans, the linearization accuracy is reduced.
Measurement Input Group 4 (NTC Path)
Customer Table |
400 W to 40 kW |
£ 0,15 % |
£ 0,1´10 -3 1/K |
Anschlussart |
2-wire circuit |
|
|
Measuring current |
ca.0,1 mA |
Measurement input group 5
Designation |
Measuring range |
Measurement accuracy |
Ambient temperature influence |
ITS |
|
Ni1000 DIN 43760:1987-09 |
-60 to +250 °C |
£ 0,25 % |
£ 0,1´10 -3 1/K Deviation of 22 °C |
68 |
|
LG-Ni1000 Landis & Gyr TK5000 (Siemens HKL) |
-60 to +250 °C |
£ 0,25 % |
£ 0,1´10 -3 1/K Deviation of 22 °C |
|
|
Kundentabelle |
150 W to 3000 W |
£ 0,25 % |
|||
Sensor Line Resistance |
≤ 30 W per Line |
||||
Connection Type |
2-wire circuit |
||||
Besonderheiten |
also programmable in °F |
||||
a The accuracy specifications refer to the maximum measuring range. With smaller measuring spans, the linearization accuracy is reduced.
Measuring Circuit Monitoring
In the event of an error, the outputs assume defined states (configurable).
Transducer Probe/cable breakage |
Probe/line short circuit |
|
Resistance thermometer |
is detected |
is detected |
KTY 2X-6 |
is detected |
is detected |
Thermoelement (einzeln) |
is detected |
is not detected |
Strom 4 to 20 mA 0 to 20 mA |
is detected is not detected |
is detected is not detected |
NTC Railway Application |
is detected |
is detected |
Ni1000, LG-Ni1000 |
is detected |
is detected |
Digital Input and Digital Output
Designation |
Funktion |
Potential-free contact (option) or PhotoMOS®-Relais (Option) |
For connection to a commercially available switch or contact Switch-on resistance < 1 k Switch-off resistance > 50 k |
max. DC 45 V, 200 mA, max. AC 30 V, 200 mA |
|
Relaisausgang |
Relay (changeover) AC 250 V, 10 A (resistive load) 150000 circuits at nominal load |
Display
Type, Resolution |
Dot matrix LCD display with 64 × 80 pixels |
Settings |
Contrast, brightness and function of the backlight |
Case
Installation height |
maximum 2000 m above sea level |
Housing type, material |
Plastic housing, polycarbonate according to DIN EN 45545 (halogen-free, use indoors only)) |
Flammability class |
UL94 V0 |
Electrical connection |
About Print Clamps with Push-In Technology |
Mounting on |
DIN rail 35 mm × 7.5 mm according to DIN IEC 60715 |
Tight-to-close mounting |
allowed |
Installation position |
vertical (vertical) |
Protection |
IP20 according to DIN EN 60529 |
Weight |
ca. 110 g |
Electric Dating
Power supply |
AC 230 V, +10/-15 %, 48 to 63 Hz oder AC 115 V, +10/-15 %, 48 to 63 Hz oder |
DC 12 bis 24 V +15/-15 %a / AC 24 V +15/-15 %, 48 to 63 Hz (The device must only be connected to SELV or PELV circuits) |
|
Power consumption |
with power supply 230 V: max. 1,5 W, 2,0 VA |
|
with power supply 115 V: max. 1,5 W, 2,0 VA |
|
with power supply DC 12 bis 24 V: max. 1,2 W |
|
with power supply AC 24 V +15/-15 %: max. 0,8 W, 1,8 VA |
Inputs and Outputs |
max. 2.5 mm2, wire or stranded wire with ferrule |
Leiterquerschnitt |
|
Electrical safety |
according to DIN EN 61010-1 Surge category III, pollution degree 2 |
Analogue inputs |
Connection to SELV (secondary circuits) only |
Sampling Cycle |
250 ms |
Speeds |
2nd order digital filter; Filter time constant adjustable from 0 to 100.0 s |
Accuracy timer and BePower hour counter |
1 % |
a Only DC 24V +15/-15% is permitted as DC supply voltage for railway applications (type suffix 950)
Environmental impact
Operating and storage temperature range |
-40 to +55 °C (display to min. -10 °C), -40 to +70 °C |
Climatic resistance |
£ 85% relative humidity on an annual average without condensation |
Electromagnetic compatibility Emission Stability |
nach din EN 61326-1, din EN 50121-1 / 50121-3-2 Class Ba Industrial Requirement |
a The product is suitable for industrial use as well as for household and small businesses.
Approvals/Certification Marks
Mark |
Checkpoint |
Certificate/Verification Number |
Test basis |
gilt für |
c UL us |
Underwriters Laboratories |
E201387 |
UL 61010-1 |
alle Baugruppen |
Data logger
The configuration and data logger data are stored in the EEPROM. They remain in place after a power failure.
Recording Rate |
Recording Duration |
1 min |
approx. 1 day, 20 hours |
5 min |
approx. 9 days, 8 hours |
15 min |
approx. 28 days, 2 hours |
30 min |
approx. 1 Monat, 25 Tage |
60 min |
approx. 3 monate, 9 fog |