Skip to main content Skip to search Skip to main navigation

JUMO eTRON T100 for DIN-rail mounting (1 relay output, changeover contact, 10 A)

Article number: 802121
Our service hotline – We are here for you 📞 +49 (0) 5121 7609 99

Product information "JUMO eTRON T100 for DIN-rail mounting (1 relay output, changeover contact, 10 A) "

JUMO eTRON T100 – electronic thermostat with timer function (DIN rail mounting, type: 701052/8-01-02-00/000)

The electronic thermostat JUMO eTRON T100 is designed for mounting on a 35 mm DIN rail and is suitable for compact installations in control cabinets as well as for industrial applications with limited space.

In this version, temperature measurement is carried out via resistance thermometers (Pt100, Pt1000 or KTY2X-6 in 2-wire connection). The device enables reliable temperature monitoring and can be used as a heating or cooling thermostat depending on the application.

The integrated timer function allows switching operations to be controlled over time or specifically limited. This enables processes to be automated and adapted to individual requirements.

All relevant values such as actual and setpoint temperature as well as the switching status are displayed simultaneously on a backlit dot matrix display (64 × 80 pixels). The menu navigation is clearly structured and available in multiple languages (German, English, French, Spanish).

Operation is carried out via four buttons on the front of the device. Push-in terminals are available for electrical installation, enabling quick and secure wiring.

Equipment of this device variant

  • Input for Pt100, Pt1000 and KTY2X-6
  • Mounting on 35 mm DIN rail
  • 1 relay output (changeover contact, AC 250 V, 10 A)
  • Power supply: AC 230 V (+10 / -15 %), 48–63 Hz
  • Dot matrix display (64 × 80 pixels)

Functions and features

The eTRON T100 offers a practical set of functions for everyday use:

  • Timer function for time-dependent control of heating or cooling processes
  • Limit value monitoring to safeguard processes
  • Data logger function for recording measured values
  • Service and operating hour counter for monitoring usage

Configuration

Parameterization can be carried out directly on the device using the operating buttons or via the setup program.

The setup program enables:

  • easy adjustment of parameters
  • reading and transferring of settings
  • support during commissioning

In addition, a customer-specific linearization of the measured values can be performed.

Special features of the JUMO eTRON T100

  • compact design for DIN rail mounting
  • easy operation and clear display
  • integrated timer function for flexible control
  • reliable switching performance via 10 A relay
  • reduced, clear equipment without additional options
  • resistance thermometers and thermocouples can also be programmed in °F

Dimensions

Height 3,2 cm
Length 11,2 cm
Width 7,9 cm

Weight

Weight 194 g

Other attributes

Country of origin DE
Customs tariff number 90321020
Eingang Widerstandsthermometer Pt100, Pt1000, KTY2X-6
Spannungsversorgung AC 230 V, +10/-15 %, 48 bis 63 Hz
Technical data:

Analog Input

The following measurement input variants can be ordered.

Measurement input group 1 (resistance thermometer)

 

Designation                                 Standard

Measuring range

Messgenauigkeita

Ambient temperature influence

ITS

Pt100, Pt1000 in                           IEC 60751:2008

2-/3-Conductor circuit

 

-200 to +600 °C

 

£ 0,25 %

 

£ 0,1´10 -3 1/K

 

90

KTY 2X-6 in 2-Conductor circuit

-50 to +150 °C

£ 1%

£ 0,1´10 -3 1/K

-

Customer Table

150 W to 3000 W

£ 0,25 %

£ 0,1´10 -3 1/K

-

 

Measuring current

ca. 0,5 mA

Sensor Line Resistance

30 W je Cable for 2- and 3-wire circuits

Line Balancing

Not required for 3-wire circuit. In the case of a 2-wire circuit, the line adjustment is carried out by software by entering a fixed line resistance.

Particularities

also programmable in °F

a The accuracy specifications refer to the maximum measuring range. With smaller measuring spans, the linearization accuracy is reduced.

Measurement input group 2 (thermocouple)

 

Designation

Norm

Measuring range

Messgenauigkeita

Ambient Temperature Influence

ITS

Fe-CuNi “L”

DIN 43710:1985-12

-200 to +900 °C

±0,4 %

£ 0,1´10 -3 1/K

68

Fe-CuNi “J”

DIN EN 60584-1:2014

-210 to +1200 °C

±0,4 % ab -100 °C

£ 0,1´10 -3 1/K

90

NiCr-Ni “K”

DIN EN 60584-1:2014

-270 to +1300 °C

±0,4 % ab -80 °C

£ 0,1´10 -3 1/K

90

Customer Table

-15 to 75 mV

±0,4 %

£ 0,1´10 -3 1/K

-

 

Measuring range start/end

within the limits in 0.1 K increments

Comparison Agent

interne Messung über Pt1000 oder extern konstant 0 °C

Reference Point Accuracy (Internal)

±1 K

Particularities

also programmable in °F

a The accuracy specifications refer to the maximum measuring range. With smaller measuring spans, the linearization accuracy is reduced.

b The ambient temperature influence is valid in the range of -20 to +55 °C.

Measurement input group 3 (unit signal)

 

Designation

Measuring range

Measurement accuracy

Ambient temperature influence

Strom (Spannungsabfall £ 2,5 V), frei skalierbar

0 to 20 mA

4 to 20 mA

£ 0,125 %

£ 0,1´10 -3 1/K

Abweichung von 22 °C

Customer Table

0 to 20 mA

£ 0,125 %

Particularities

Skalierung einstellbar

a The accuracy specifications refer to the maximum measuring range. With smaller measuring spans, the linearization accuracy is reduced.

 

Measurement Input Group 4 (NTC Path)

 

 

Customer Table

400 W to 40 kW

£ 0,15 %

£ 0,1´10 -3 1/K

Anschlussart

2-wire circuit

 

 

Measuring current

ca.0,1 mA

Measurement input group 5

 

Designation

Measuring range

Measurement accuracy

Ambient temperature influence

ITS

Ni1000                                         DIN 43760:1987-09

-60 to +250 °C

£ 0,25 %

£ 0,1´10 -3 1/K

Deviation of 22 °C

68

LG-Ni1000                                  Landis & Gyr TK5000 (Siemens HKL)

-60 to +250 °C

£ 0,25 %

£ 0,1´10 -3 1/K

Deviation of 22 °C

 

Kundentabelle

150 W to 3000 W

£ 0,25 %

Sensor Line Resistance

30 W per Line

Connection Type

2-wire circuit

Besonderheiten

also programmable in °F

a The accuracy specifications refer to the maximum measuring range. With smaller measuring spans, the linearization accuracy is reduced.

 

Measuring Circuit Monitoring

In the event of an error, the outputs assume defined states (configurable).

 

Transducer                                 Probe/cable breakage

Probe/line short circuit

Resistance thermometer

is detected

is detected

KTY 2X-6

is detected

is detected

Thermoelement (einzeln)

is detected

is not detected

Strom

4 to 20 mA

0 to 20 mA

 

is detected

is not detected

 

is detected

is not detected

NTC Railway Application

is detected

is detected

Ni1000, LG-Ni1000

is detected

is detected

Digital Input and Digital Output

 

Designation

Funktion

Potential-free contact (option)

or

PhotoMOS®-Relais (Option)

For connection to a commercially available switch or contact Switch-on resistance < 1 k Switch-off resistance > 50 k

max. DC 45 V, 200 mA, max. AC 30 V, 200 mA

Relaisausgang

Relay (changeover) AC 250 V, 10 A (resistive load)

150000 circuits at nominal load

Display

 

Type, Resolution

Dot matrix LCD display with 64 × 80 pixels

Settings

Contrast, brightness and function of the backlight

 

Case

 

Installation height

maximum 2000 m above sea level

Housing type, material

Plastic housing, polycarbonate according to DIN EN 45545 (halogen-free, use indoors only))

Flammability class

UL94 V0

Electrical connection

About Print Clamps with Push-In Technology

Mounting on

DIN rail 35 mm × 7.5 mm according to DIN IEC 60715

Tight-to-close mounting

allowed

Installation position

vertical (vertical)

Protection

IP20 according to DIN EN 60529

Weight

ca. 110 g

Electric Dating

 

Power supply

AC 230 V, +10/-15 %, 48 to 63 Hz oder

AC 115 V, +10/-15 %, 48 to 63 Hz oder

DC 12 bis 24 V +15/-15 %a / AC 24 V +15/-15 %, 48 to 63 Hz

(The device must only be connected to SELV or PELV circuits)

Power consumption

with power supply 230 V: max. 1,5 W, 2,0 VA

 

with power supply 115 V: max. 1,5 W, 2,0 VA

 

with power supply DC 12 bis 24 V: max. 1,2 W

 

with power supply AC 24 V +15/-15 %: max. 0,8 W, 1,8 VA

Inputs and Outputs

 

max. 2.5 mm2, wire or stranded wire with ferrule

Leiterquerschnitt

Electrical safety

according to DIN EN 61010-1

Surge category III, pollution degree 2

Analogue inputs

Connection to SELV (secondary circuits) only

Sampling Cycle

250 ms

Speeds

2nd order digital filter; Filter time constant adjustable from 0 to 100.0 s

Accuracy timer and BePower hour counter

1 %

a Only DC 24V +15/-15% is permitted as DC supply voltage for railway applications (type suffix 950)

 

Environmental impact

 

Operating and storage temperature range

-40 to +55 °C (display to min. -10 °C), -40 to +70 °C

Climatic resistance

£ 85% relative humidity on an annual average without condensation

Electromagnetic compatibility

Emission

Stability

nach din EN 61326-1, din EN 50121-1 / 50121-3-2

Class Ba Industrial Requirement

a The product is suitable for industrial use as well as for household and small businesses.

 

Approvals/Certification Marks

 

Mark

Checkpoint

Certificate/Verification Number

Test basis

gilt für

c UL us

Underwriters Laboratories

E201387

UL 61010-1

alle Baugruppen

Data logger

The configuration and data logger data are stored in the EEPROM. They remain in place after a power failure.

 

Recording Rate

Recording Duration

1 min

approx. 1 day, 20 hours

5 min

approx. 9 days, 8 hours

15 min

approx. 28 days, 2 hours

30 min

approx. 1 Monat, 25 Tage

60 min

approx. 3 monate, 9 fog