Skip to main content Skip to search Skip to main navigation
Our service hotline – We are here for you 📞 +49 (0) 5121 7609 99

Product information "JUMO diraVIEW 108 (landscape format 96 x 48 mm, 1 analog input, 2 relays, 1 digital input, 1 digital input/output) "

JUMO diraVIEW 108 – Digital Indicator (Type: 701513/8-0000-25/000, Low Voltage)

This version is designed for low-voltage operation (AC/DC 20–30 V) and can therefore be optimally integrated into systems with corresponding power supply concepts.

The JUMO diraVIEW 108 is a compact digital indicator in horizontal format 96 × 48 mm for capturing, displaying, and monitoring process variables. Thanks to the universal analog input, the device can be used flexibly for different signal types and is suitable for a wide range of industrial applications.

In addition to displaying measured values, the device also performs monitoring and control functions. Two integrated relay outputs enable the direct implementation of switching tasks, for example when defined limit values are reached.

The display is provided via two easy-to-read 18-segment LCD displays. Additional display elements also indicate the status of the outputs as well as active functions such as timers or limit value monitoring. Operation is carried out via a membrane keypad with four keys. Thanks to protection class IP65, the device is suitable for industrial environments.

Equipment of this device variant

  • 1 universal analog input
  • 2 digital inputs (digital input 1 can alternatively be used as a logic output)
  • 2 relay outputs (normally open contacts)
  • 1 logic output 0/14 V (alternative to digital input 1)
  • Power supply: AC/DC 20–30 V, 48–63 Hz
  • Display via 2 × 18-segment LCD
  • Installation format: 96 × 48 mm (horizontal format)

Functions and possibilities

The diraVIEW 108 offers numerous functions for evaluating and monitoring measured values:

  • Min./max. value display and storage
  • Hold function for retaining measured values
  • Tare function, also suitable for weighing applications
  • Timer function for implementing time-dependent processes
  • Monitoring of up to 4 limit values with various alarm options

In addition, digital signals can be processed flexibly and logically linked with one another.

Signal processing & flexibility

All signals are managed internally via selectors. This allows input and output signals to be flexibly assigned and individually configured for different applications.

Interfaces & configuration

The device features a USB device interface for connection to a PC. Parameterization is carried out via the setup program, with which:

  • Settings can be created and transferred
  • Device data can be read out and saved
  • Wiring diagrams can be generated automatically

During configuration, the power supply is provided via the USB interface.

Optional interfaces such as RS485 or Ethernet are available to integrate the device into higher-level systems.

Advantages

  • Low-voltage operation for flexible application possibilities
  • Universal analog input for various signal types
  • Two relay outputs for extended switching functions
  • Combination of display, monitoring, and control
  • Robust design for industrial applications

Application areas

  • Use in systems with low-voltage power supply (e.g. 24 V systems)
  • Integration into mobile or autonomous systems with limited energy supply
  • Monitoring of process values in control systems with DC voltage
  • Use in safety-related applications with low voltage
  • Integration into compact control cabinets with 24 V infrastructure
  • Evaluation and display of sensor signals in automation systems
  • Implementation of switching tasks via relays when limit values are exceeded
  • Combination of display and control in energy-optimized systems
Ordering Information
Position Code Description
(1) Basic type
701510 Type 701510 (Format 132: 48 × 24 mm)
1 analog input, 2 digital inputs (digital input 1 alternatively used as logic output), 1 relay (NO contact), 1 logic output 0/14 V (alternative to digital input 1)
Incl. timer, min./max. value display, hold function, and tare function.
701511 Type 701511 (Format 116: 48 × 48 mm)
1 analog input, 2 digital inputs (digital input 1 alternatively used as logic output), 2 relays (NO contacts), 1 logic output 0/14 V (alternative to digital input 1)
Incl. timer, min./max. value display, hold function, and tare function.
701512 Type 701512 (Format 108H: 48 × 96 mm)
1 analog input, 2 digital inputs (digital input 1 alternatively used as logic output), 2 relays (NO contacts), 1 logic output 0/14 V (alternative to digital input 1)
Incl. timer, min./max. value display, hold function, and tare function.
701513 Type 701513 (Format 108Q: 96 × 48 mm)
1 analog input, 2 digital inputs (digital input 1 alternatively used as logic output), 2 relays (NO contacts), 1 logic output 0/14 V (alternative to digital input 1)
Incl. timer, min./max. value display, hold function, and tare function.
701514 Type 701514 (Format 104: 96 × 96 mm)
1 analog input, 2 digital inputs (digital input 1 alternatively used as logic output), 2 relays (NO contacts), 1 logic output 0/14 V (alternative to digital input 1)
Incl. timer, min./max. value display, hold function, and tare function.
(2) Version
8 Standard with factory settingsa
9 Customer-specific configuration (specifications in plain text)
(3) Option 1b
0Not assigned
11 relay (NO contact) (only for type 701511)
21 logic output 0/14 V (only for types 701511–701514)
41 RS485 interface (Modbus RTU)
(4) Option 2b
0Not assigned
11 relay (NO contact)
21 logic output 0/14 V
31 analog output
7 1 Ethernet interface (Modbus TCP, Modbus RTU/ASCII via TCP/IP)
Only for types 701512, 701513, and 701514. Option 1 is omitted.
(5) Option 3b (only for types 701512–701514)
0Not assigned
11 relay (NO contact)
21 logic output 0/14 V
51 PhotoMOS® relayc
(6) Option 4b (only for types 701512–701514)
0Not assigned
11 relay (NO contact)
21 logic output 0/14 V
51 PhotoMOS® relayc
61 relay (NO contact) with extended contact life
(7) Power supply
23 AC 110 to 240 V (+10/-15%), 48 to 63 Hz
25 AC/DC 20 to 30 V, 48 to 63 Hz
(8) Type extras
000Without type extra
062With DNV-GL approvald
049With BV approvald
214Mathematics and logic module
221Structured Text
Notes
  1. a The device language can be selected (German, English, French, Spanish).
  2. b Options cannot be retrofitted and must be specified when ordering.
  3. c PhotoMOS® is a registered trademark of Panasonic Corporation.
  4. d Available only for type 701511 with AC/DC 20–30 V power supply (approval valid for DC operation only) and type 701514 with AC 110–240 V power supply. Not available in combination with Ethernet interface. Approval is valid exclusively for panel mounting.
Order Code Structure
(1)
Basic type
(2)
Version
(3)
Option 1
(4)
Option 2
(5)
Option 3
(6)
Option 4
(7)
Power supply
(8)
Type extras
Order code (1) / (2) - (3) (4) (5) (6) - (7) / (8), …a
Order example 701514 / 8 - 4 3 5 6 - 23 / 214, …
a Multiple type extras are listed consecutively and separated by commas.
Technical data:
Technical Specifications – Analogue Input for Thermocouples
Designation Type standard ITS Measuring range Accuracya
Fe-CuNi „L“ DIN 43710 (1985) IPTS-68 -200 to +900 °C ≤ 0,25 %
Fe-CuNi „J“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -210 to +1200 °C ≤ 0,25 % from -100 °C
Cu-CuNi „U“ DIN 43710 (1985) IPTS-68 -200 to +600 °C ≤ 0,25 % from -100 °C
Cu-CuNi „T“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +400 °C ≤ 0,25 % from -150 °C
NiCr-Ni „K“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +1300 °C ≤ 0,25 % from -80 °C
NiCr-CuNi „E“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +1000 °C ≤ 0,25 % from -80 °C
NiCrSi-NiSi „N“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +1300 °C ≤ 0,25 % from -80 °C
Pt10Rh-Pt „S“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -50 to +1768 °C ≤ 0,4 % from 20 °C
Pt13Rh-Pt „R“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -50 to +1768 °C ≤ 0,25 % from 50 °C
Pt30Rh-Pt6Rh „B“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -50 to +1820 °C ≤ 0,25 % from 400 °C
W5Re-W26Re „C“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 0 to 2315 °C ≤ 0,25 % from 500 °C
W3Re-W25Re „D“ ASTM E1751M-15 ITS-90 0 to 2315 °C ≤ 0,25 % from 500 °C
W5Re-W20Re „A1“ GOST R 8.585-2001 ITS-90 0 to 2500 °C ≤ 0,25 % from 500 °C
Chromel®-Copel „L“ GOST R 8.585-2001 ITS-90 -200 to +800 °C ≤ 0,25 % from -80 °C
Chromel®-Alumel® „K“ GOST R 8.585-2001 ITS-90 -270 to +1300 °C ≤ 0,25 % from -80 °C
a The accuracy applies to the measurement range.
Technical additional data – thermocouples
Parameter Description
Effect of ambient temperature ≤ 100 ppm/K
Comparison site internal or external (constant)
Reference point temperature (external) 0 to 100 °C (adjustable)
sampling cycle 150 ms
Input filter second-order digital filter;
Filter constant adjustable from 0 to 100.0 s
Technical specifications – Resistance temperature sensors
Designation standard ITS Connection type Measuring range Accuracya Measuring current
Pt100 DIN EN 60751:2009
IEC 60751:2008
ITS-90 2-wire connection -200 to +850 °C ≤ 0,2 % 500 µA
3-wire connection -200 to +850 °C ≤ 0,1 % 500 µA
Pt1000 DIN EN 60751:2009
IEC 60751:2008
ITS-90 2-/3-wire connection -200 to +850 °C ≤ 0,1 % 50 µA
Pt100 GOST 6651-2009 A.2 ITS-90 2-wire connection -200 to +850 °C ≤ 0,2 % 500 µA
3-wire connection -200 to +850 °C ≤ 0,1 % 500 µA
KTY – – 2-wire connection -53 to +153 °C ≤ 2,0 % 50 µA
a The accuracy applies to the measurement range.
Technical specifications – Resistance temperature sensors
Parameter Description
Effect of ambient temperature ≤ 50 ppm/K
Sensor lead resistance max. 30 Ω per line
sampling cycle 150 ms
Input filter second-order digital filter;
Filter constant adjustable from 0 to 100.0 s
Technical specifications – Resistor potentiometer / Resistor / Potentiometer
Designation Measuring range Accuracya Measuring current
resistance potentiometer / WFG 0 to 4000 Ω ≤ 0,1 % 50 µA
Resistor / potentiometer 0 to 400 Ω ≤ 0,1 % 500 µA
0 to 4000 Ω ≤ 0,1 % 50 µA
a The accuracy refers to the maximum measuring range. For small measuring ranges, the linearity accuracy is reduced.
Technical data – resistance potentiometer / resistor / potentiometer
Parameter Description
Effect of ambient temperature ≤ 100 ppm/K
Connection type Resistance potentiometer / WFG: three-wire connection
Resistor / potentiometer: two-/three-wire connection
Sensor lead resistance max. 30 Ω per line
sampling cycle 150 ms
Input filter second-order digital filter;
Filter constant adjustable from 0 to 100.0 s
Technical specifications – Voltage and current (standard signals)
Description Measurement range accuracya Input resistance or load voltage
Voltage 0 to 10 V ≤ 0,1 % > 500 kΩ
2 to 10 V ≤ 0,1 % > 500 kΩ
Electricity 4 to 20 mA ≤ 0,1 % < 2,5 V
0 to 20 mA ≤ 0,1 % < 2,5 V
a The accuracy refers to the maximum measuring range. For small measuring ranges, the linearity accuracy is reduced.
Technical additional data – voltage, current (standard signals)
Parameter Description
The effect of ambient temperature ≤ 100 ppm/K
Measurement range under/over-range in accordance with NAMUR recommendation NE 43
(4–20 mA current input only)
sampling cycle 150 ms
Input filter second-order digital filter;
Filter constant adjustable from 0 to 100.0 s
Circuit monitoring – behaviour in the event of a fault
measuring transducer Value below the measurement range Exceeding the measurement range Short circuit (sensor/cable) Break (sensor/cable) Reverse polarity
Resistance thermometer ++ ++ ++ ++ ---
resistor / potentiometer --- ++ --- ++ ---
Potentiometer / WFG --- ++ (+)a (+)b ---
thermocouple ++ ++ --- ++ (+)c
Current 0 to 20 mA --- ++ --- --- ---
Current 4 to 20 mA ++ ++ ++ ++ ++
voltage 0 to 10 V --- ++ --- --- ++
voltage 2 to 10 V ++ ++ ++ ++ ++
++ = is recognised  |  --- = is not recognised  |  (+) = is recognised conditionally
a is not recognised in all combinations
b A break in the measurement current path is not detected
c depending on the selected characteristic curve
Technical data – digital inputs
Parameter Description
input for volt-free contact Contact closed: input is active (RON < 1 kΩ)
Contact open: input inactive (ROFF > 50 kΩ)
sampling cycle 150 ms
Technical data – analogue output
Parameter Description
Voltage – output signal / load resistance DC 0(2) to 10 V
> 500 Ω
Current – output signal / load resistance DC 0(4) to 20 mA
< 450 Ω
Accuracy ≤ 0,5 %
influence of ambient temperature ≤ 150 ppm/K
Technical data – digital outputs
output type switching capacity / output signal Contact service life
relay (normally open contact) max. 3 A at 230 V AC or 30 V DC, resistive load 150,000 switching operations at rated load
– 350,000 switching operations at 1 A
– –
relay (normally open contact) with extended contact life max. 3 A at 230 V AC, resistive load 300,000 switching operations at rated load
– 1,500,000 switching operations at 1 A
– –
logic output DC 0/14 V ±15 %
max. 20 mA per output (at 14 V nominal voltage)
–
PhotoMOS®-Relaisa max. 200 mA at 30 V AC or 45 V DC;
not short-circuit proof
–
a PhotoMOS is a registered trademark of Panasonic Corporation.
Technical data – interfaces
interface Parameter value
USB-Device connector type Micro-B (socket)
Standard Low-Speed, Full-Speed
max. cable length 5 m
RS485 baud rate 9600, 19200, 38400, 115200
data format 8/1n, 8/1e, 8/1o, 8/2n
protocol Modbus RTU as slave
Ethernet connector type RJ45 (socket)
transmission rate 10 Mbit/s, 100 Mbit/s
protocol TCP/IP, DHCP;
Modbus-TCP, Modbus-RTU/ASCII over TCP, as Slave
Technical data – display (18-segment LCD)
Type Format Digit height of the upper display Digit height on the lower display
701510 132 7,2 mm 3,8 mm
701511 116 12,3 mm 5,9 mm
701512 108H 11,5 mm 8,5 mm
701513 108Q 16,5 mm 9 mm
701514 104 24,8 mm 12 mm
Additional technical data – display
Parameter Description
Color top display: white; bottom display: green
Figures including decimal places top display: 4;
lower display: 4 (5 for type 701510, 8 for type 701511)
decimal places 0, 1, 2, 3 or automatically (configurable)
Technical specifications – pixel-matrix LCD display (models 701512, 701513, 701514 only)
Type Format Pixel fields
701512 108H 2 Rows of 9 pixel fields each
701513 108Q 2 Rows of 8 pixel fields each
701514 104 2 Rows of 11 pixel fields each
Technical additional data – pixel-matrix LCD display
Parameter Value
Number of pixels per field 8 x 5
Color white
Technical specifications – Electrical specifications
Parameter Variant / Type Value
Power supply Variant 1 AC 110 to 240 V +10/-15 %, 48 to 63 Hz
Variant 2 (see the type plate) AC/DC 20 to 30 V, 48 to 63 Hz
Electrical safety in accordance with DIN EN 61010, Part 1;
Surge category II up to 300 V mains voltage, pollution degree 2
Protection class I with internal isolation to SELV
Power consumption Type 701510 (Format 132) at AC 110 to 240 V: max. 3,5 W
at AC/DC 20 to 30 V: max. 3,0 W
Type 701511 (Format 116) at AC 110 to 240 V: max. 4,1 W
at AC/DC 20 to 30 V: max. 3,7 W
Types 701512, 701513 (Formats 108H, 108Q) at AC 110 to 240 V: max. 5,8 W
at AC/DC 20 to 30 V: max. 5,7 W
Type 701514 (Format 104) at AC 110 to 240 V: max. 6,6 W
at AC/DC 20 to 30 V: max. 6,7 W
Electrical connection rear via spring-cage terminals (push-in technology)
Conductor cross-section solid or stranded wire (without ferrule) min. 0,2 mm², max. 1,5 mm²
stranded wire with ferrule without plastic collar: min. 0,2 mm², max. 1,5 mm²
with plastic collar: min. 0,2 mm², max. 0,75 mm²
Stripping length 8 mm
Technical data – environmental influences
Parameter Value / classification
Ambient temperature range
Storage -30 to +70 °C
Operation -10 to +55 °C
Installation height max. 2000 m AMSL (above mean sea level)
Climatic environmental conditions in accordance with DIN EN 60721-3, with an extended temperature range
climate resistance ≤ 90 % relative humidity without condensation
storage in accordance with class 1K2
Operation in accordance with class 3K3
Mechanical environmental conditions in accordance with DIN EN 60721-3
storage in accordance with class 1M2
Transport in accordance with class 2M2
Operation in accordance with class 3M3
Electromagnetic compatibility (EMC) in accordance with DIN EN 61326-1
Emitted interference Class A – for industrial use only –
Immunity to interference industrial requirement
Technical data – enclosure
Parameter Type / variant Value
Enclosure type Plastic enclosure for panel mounting in accordance with DIN IEC 61554 (indoor use)
Front panel made of plastic with membrane keypad
Panel thickness 1 to 10 mm
Enclosure mounting in the panel using the supplied mounting frame or the two mounting elements
Operating position anya
Ingress protection rating in accordance with DIN EN 60529, front IP65, rear IP20
Weight Type 701510 (Format 132) max. 85 g
Type 701511 (Format 116) max. 120 g
Type 701512 (Format 108H) max. 160 g
Type 701513 (Format 108Q) max. 160 g
Type 701514 (Format 104) max. 220 g
a The maximum permissible ambient temperature applies only when the display is installed in a vertical position.
Technical data – approvals and certification marks
Certification marks Test authority Certificates / approval numbers Test basis Applies to
c UL us Underwriters Laboratories E201387 UL 61010-1 (3. Ed.),
CAN/CSA-22.2 No. 61010-1 (3. Ed.)
all variants
DNV GL DNV GL TAA00001B3 Class Guideline DNVGL-CG-0339 Type 701511 (DC 20 bis 30 V)
and Type 701514 (AC 110 bis 240 V), without Ethernet interface, panel mounting
BUREAU VERITAS Bureau Veritas 53627/A0 BV Bureau Veritas Rules for the Classification of Steel Ships Type 701511 (DC 20 bis 30 V)
and Type 701514 (AC 110 bis 240 V), without Ethernet interface, panel mounting
The device is approved if the relevant certification mark is displayed on the device.