Product information "JUMO diraVIEW 108 (landscape format 96 x 48 mm, 1 analog input, 2 relays, 1 digital input, 1 digital input/output) "

JUMO diraVIEW 108 – Digital Indicator (Type: 701513/8-0000-23/000)

This digital indicator consists of five freely configurable and universally applicable devices in different DIN formats for displaying temperature, pressure, and other process variables.

The JUMO diraVIEW 108 is a versatile digital indicator in horizontal format 96 × 48 mm for capturing, displaying, and monitoring a wide range of process variables. Thanks to the universal analog input, the device can be used flexibly for different signal types and is suitable for a variety of industrial applications.

In addition to pure display, the device also enables direct processing of measured values. Two integrated relay outputs are available to implement switching functions at defined limit values. This allows the diraVIEW 108 to be used not only as a display device, but also as a monitoring and control unit.

The display is clearly presented via two 18-segment LCD displays. Additional display elements also indicate the status of the outputs as well as active functions such as timers or limit value monitoring. Operation is carried out via a front-mounted membrane keypad with four keys. Thanks to protection class IP65, the device is also suitable for demanding environments.

Equipment of this device variant

  • 1 universal analog input
  • 2 digital inputs (digital input 1 can alternatively be used as a logic output)
  • 2 relay outputs (normally open contacts)
  • 1 logic output 0/14 V (alternative to digital input 1)
  • Power supply: AC 110–240 V (+10 / -15 %), 48–63 Hz
  • Display via 2 × 18-segment LCD
  • Installation format: 96 × 48 mm (horizontal format)

Functions and possibilities

The diraVIEW 108 offers a comprehensive range of functions for monitoring and evaluating measured values:

  • Min./max. value storage for continuous analysis
  • Hold function for retaining measured values
  • Tare function, also suitable for weighing applications
  • Timer function for implementing time-controlled processes
  • Monitoring of up to 4 limit values with a wide range of alarm functions

In addition, digital signals can be processed flexibly and logically linked with one another.

Signal processing & flexibility

The internal signals are managed via selectors, enabling flexible assignment of inputs, outputs, and functions. This allows the device to be individually adapted to different applications.

Interfaces & configuration

The device features a USB device interface for connection to a PC. Configuration is carried out via the setup program, with which:

  • Parameters can be created and transferred
  • Device data can be read out and saved
  • Wiring diagrams can be generated automatically

During parameterization, the power supply is provided via the USB interface.

Advantages

  • Versatile use thanks to universal analog input
  • Two relay outputs for flexible switching tasks
  • Combination of display, monitoring, and control
  • Extensive additional functions such as timer, min/max, and tare
  • Robust design for industrial environments

Possible application areas

  • Monitoring and display of temperature values in industrial processes
  • Control of pressure, level, or flow signals
  • Use in machines and systems with available mains voltage (110–240 V)
  • Use in automation systems for process monitoring
  • Monitoring of analog sensor signals in continuous processes

Dimensions

Height 6,7 cm
Length 10,6 cm
Width 7,6 cm

Weight

Weight 215 g

Other attributes

Country of origin DE
Customs tariff number 90303370
Format 96 x 48 mm
Spannungsversorgung AC 110 bis 240 V + 10/-15% , 48 bis 63Hz
Technical data:

Analog Input

Thermocouples

Designation

Typ

Norm

ITS

Measuring range

Accuracy

Fe-CuNi

„L“

DIN 43710 (1985)

IPTS-68

-200 to +900 C

£ 0,25 %

Fe-CuNi

„J“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-210 to +1200 °C

£ 0,25 % off -100 °C

Cu-CuNi

„U“

DIN 43710 (1985)

IPTS-68

-200 to +600 °C

£ 0,25 % off -100 °C

Cu-CuNi

„T“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-270 to +400 °C

£ 0,25 % off -150 °C

NiCr-Ni

„K“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-270 to +1300 °C

£ 0,25 % off -80 °C

NiCr-CuNi

„E“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-270 to +1000 °C

£ 0,25 % off -80 °C

NiCrSi-NiSi

„N“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-270 to +1300 °C

£ 0,25 % off -80 °C

Pt10Rh-Pt

„S“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-50 to +1768 °C

£ 0,4 % off 20 °C

Pt13Rh-Pt

„R“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-50 to +1768 °C

£ 0,25 % off 50 °C

Pt30Rh-Pt6Rh

„B“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-50 to +1820 °C

£ 0,25 % off 400 °C

W5Re-W26Re

„C“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

0 to 2315 °C

£ 0,25 % off 500 °C

W3Re-W25Re

„D“

ASTM E1751M-15

ITS-90

0 to 2315 °C

£ 0,25 % off 500 °C

W5Re-W20Re

„A1“

GOST R 8.585-2001

ITS-90

0 to 2500 °C

£ 0,25 % off 500 °C

Chromel®-Copel

„L“

GOST R 8.585-2001

ITS-90

-200 to +800 °C

£ 0,25 % off -80 °C

Chromel®-Alumel®

„K“

GOST R 8.585-2001

ITS-90

-270 to +1300 °C

£ 0,25 % off -80 °C

a  Accuracy refers to the measurement range.

 

Ambient temperature influence

£ 100 ppm/K

Comparison agency

internal or external (constant)

Comparison point temperature (ex- tern)

0 to 100 °C (adjustable)

Sampling cycle

150 ms

Eingangsfilter

2nd order digital filter; Filter constant adjustable from 0 to 100.0 s

 

Resistance thermometer

Designation

Norm

ITS

Connection type

Measuring range

Accuracy

Measuring current

Pt100

DIN EN 60751:2009

IEC 60751:2008

ITS-90

2-Ladder

-200 to +850 °C

£ 0,2 %

500 mA

3- Ladder

-200 to +850 °C

£ 0,1 %

500 mA

Pt1000

DIN EN 60751:2009

IEC 60751:2008

ITS-90

2-/3- Ladder

-200 to +850 °C

£ 0,1 %

50 mA

Pt100

GOST 6651-2009 A.2

ITS-90

2- Ladder

-200 to +850 °C

£ 0,2 %

500 mA

3- Ladder

-200 to +850 °C

£ 0,1 %

500 mA

KTY

 

 

2- Ladder

-53 to +153 °C

£ 2,0 %

50 mA

a  Accuracy refers to the measurement range.

 

Ambient temperature influence

£ 50 ppm/K

Sensor Line Resistance

max. 30 W je Line

Sampling cycle

150 ms

Speeds

2nd order digital filter; Filter constant adjustable from 0 to 100.0 s

 

Resistance Potentiometer/WFG and Resistance/Potentiometer

 

Designation

Measuring range

Accuracya

Measuring current

Widerstandspotenziometer/WFG

0 bis 4000 W

£ 0,1 %

50 mA

Widerstand/Poti

0 to 400 W

0 to 4000 W

£ 0,1 %

£ 0,1 %

500 mA

50 mA

a Accuracy refers to the maximum measurement range. At small measuring spans, the linearization accuracy is reduced.

 

Ambient temperature influence

£ 100 ppm/K

Anschlussart

 

Resistance Potentiometer/

Three-wire circuit

WFG

 

Widerstand/Poti

Two-/three-wire circuit

Sensor Line Resistance

max. 30 W per line

Sampling cycle

150 ms

Speeds

2nd order digital filter; Filter constant adjustable from 0 to 100.0 s

Voltage, current (unit signals)

 

Designation

Measuring range

Accuracy

Input resistance or load voltage

Voltage

0 to 10 V

£ 0,1 %

>  500 kW

2 to 10 V

£ 0,1 %

>  500 kW

Current

4 to 20 mA

£ 0,1 %

< 2,5 V

0 to 20 mA

£ 0,1 %

< 2,5 V

a Accuracy refers to the maximum measurement range. At small measuring spans, the linearization accuracy is reduced.

 

Ambient temperature influence

£ 100 ppm/K

Measuring range under/exceeding

according to NAMUR recommendation NE 43 (only current input 4 to 20 mA)

Sampling cycle

150 ms

Speeds

2nd order digital filter; Filter constant adjustable from 0 to 100.0 s

Measuring Circuit Monitoring

The behavior of the device in the event of a fault is configurable.

 

Transmitter

Measuring range below

Exceeding the measuring range

Short circuit (sensor/line)

Bruch (Fühler/Lei- tung)

Reverse polarity

Widerstandsthermo- meter

++

++

++

++

---

Widerstand/Poti

---

++

---

++

---

Widerstandspotenzio- meter/WFG

---

++

(+)a

(+)b

---

Thermoelement

++

++

---

++

(+)c

Strom 0 to 20 mA

---

++

---

---

---

Strom 4 to 20 mA

++

++

++

++

++

Spannung 0 to 10 V

---

++

---

---

++

Spannung 2 to 10 V

++

++

++

++

++

++ = is detected                                                                   --- = is not recognized                                                        (+) = is conditionally recognized

a  is not recognized in all combinations

b  Break in the measurement current path is not detected

c  depending on the set characteristic curve

 

Digital Inputs

 

Input for potential-free contact

Function

 

Sampling cycle

 

Contact closed: Input is active (RON < 1 kΩ)

Contact open: Receipt is inactive (ROFF > 50 kΩ)

150 ms

Analogoutput

 

Voltage

Ausgangssignal Lastwiderstand

 

DC 0(2) to

Output Signal Load Resistance 10 V

> 500 

Current

Output Signal Load Resistance

 

DC 0(4) bis 20 mA

< 450 

Accuracy

 0,5 %

Ambient temperature influence

 150 ppm/K

 

Digital outputs 

Relay (NO contact)

Switching capacity contact life

 

max. 3 A bei AC 230 V or DC 30 V, ohmsche Last

150.000 Circuits at Rated Load

350.000 Circuits at 1 A

Relays (NO contacts) with longer contact life

Schaltleistung Kontaktlebensdauer

 

 

max. 3 A bei AC 230 V, ohmsche Last

300.000 Schaltungen bei Nennlast

1.500.000 Schaltungen bei 1 A

Logic Output

Output

Strom

 

DC 0/14 V ±15 %

max. 20 mA per output (at nominal voltage 14 V)

PhotoMOS®-Relaisa

Switching capacity

 

max. 200 mA at AC 30 V or DC 45 V; not short-circuit proof

a PhotoMOS is a registered trademark of Panasonic Corporation.

 

Interfaces

 

USB-Device

 

Plug Type

Micro-B (Buchse)

Standard

Low-Speed, Full-Speed

Max. cable length

5 m

RS485

 

Baudrate

9600, 19200, 38400, 115200

Data format

8/1n, 8/1e, 8/1o, 8/2n

Protocol

Modbus-RTU as Slave

Ethernet

 

Plug Type

RJ45 (Buchse)

Übertragungsrate

10 Mbit/s, 100 Mbit/s

Protocol

TCP/IP, DHCP; Modbus-TCP, Modbus-RTU/ASCII über TCP, als Slave

 

Display

 

18-segment LCD displays

Digit height

obere Anzeige:

bottom display:

Typ 701510 (Format 132)

7,2 mm

3,8 mm

Typ 701511 (Format 116)

12,3 mm

5,9 mm

Typ 701512 (Format 108H)

11,5 mm

8,5 mm

Typ 701513 (Format 108Q)

16,5 mm

9 mm

Typ 701514 (Format 104)

24,8 mm

12 mm

Color

top display: white; Bottom display: green

Digits incl. decimal places

top display: 4; bottom display: 4 (5 for type 701510, 8 for type 701511)

Decimal places

0, 1, 2, 3 or automatically (configurable)

 

Pixel matrix LCD display (701512, 701513, and 701514 types only)

Pixel Fields

 

Typ 701512 (Format 108H)

2 rows of 9 pixel fields each

Typ 701513 (Format 108Q)

2 rows of 8 pixel fields each

Typ 701514 (Format 104)

2 rows of 11 pixel fields each

Pixelanzahl is Feld

8 x 5

Color

weiß

Electric Dating

 

Spannungsversorgung Variante 1

Variante 2

(see nameplate)

AC 110 to 240 V +10/-15 %, 48 to 63 Hz

AC/DC 20 to 30V, 48 to 63Hz

Electrical safety

according to DIN EN 61010, Part 1; Overvoltage category II up to 300 V mains voltage, contamination grade 2

Class

I with internal separation to SELV

Power consumption

at AC 110 to 240 V:

for AC/DC 20 to 30 V:

Typ 701510 (Format 132)

max. 3,5 W

max. 3,0 W

Typ 701511 (Format 116)

max. 4,1 W

max. 3,7 W

Typen 701512, 701513

(Formate 108H, 108Q)

max. 5,8 W

max. 5,7 W

Typ 701514 (Format 104)

max. 6,6 W

max. 6,7 W

Electrical connection

on the back via spring-loaded clamps (push-in technology)

Conductor cross-section

 

Wire or stranded wire

min. 0,2 mm2, max. 1,5 mm2

(without ferrule)

 

Stranded wire with ferrule

without plastic collar: min. 0,2 mm2, max. 1,5 mm2

 

mit Kunststoffkragen: min. 0,2 mm2, max. 0,75 mm2

Stripping length

8 mm

 

Environmental influences 

Ambient temperature range

Storage

Operation

 

-30 to +70 °C

-10 to +55 °C

Installation height

max. 2000 m above NN

Climatic environmental conditions Climate resistance

Storage

according to DIN EN 60721-3 with extended temperature range

£ 90 % relative humidity without condensation after class 1K2

Operation

after class 3K3

 

Mechanical environmental conditions Storage

Transport

Operation

according to DIN EN 60721-3

according to class 1M2

by class 2M2

according to class 3M3

Electromagnetic compatibility (EMV) Emission

Stability

according to DIN EN 61326-1

Class A - for industrial use only - Industry Requirement

Gehäuse

 

Housing type

Plastic enclosures for panel installation in accordance with DIN IEC 61554 (use indoors))

Cabinet front

made of plastic with membrane keypad

Panel thickness

1 to 10 mm

Housing Mounting

in the control panel using the supplied mounting frame or the two fastening elements

Usage position

Any a

Protection

according to DIN EN 60529, front IP65, rear IP20

Gewicht

 

Typ 701510 (Format 132)

max. 85 g

Typ 701511 (Format 116)

max. 120 g

Typ 701512 (Format 108H)

max. 160 g

Typ 701513 (Format 108Q)

max. 160 g

Typ 701514 (Format 104)

max. 220 g

a The maximum permissible ambient temperature only applies to installation with vertical orientation of the display.

 

Approvals and test marks

 

Mark

Checkpoint

Certificates/Test Numbers

Test basis

Applies to

c UL us

Underwriters Laboratories

E201387

UL 61010-1 (3. Ed.),

CAN/CSA-22.2 No. 61010-1

(3. Ed.)

all versions

DNV GL

DNV GL

TAA00001B3

Class Guideline DNVGL-CG-0339

Typ 701511 (DC 20 bis 30 V)

and Type 701514 (AC 110 to 240 V), without Ethernet interface, panel mounting

BUREAU VERITAS

Bureau Veritas

53627/A0 BV

Bureau Veritas Rules for the Classification of Steel Ships

The device has approval if the relevant test mark is shown on the device.