Skip to main content Skip to search Skip to main navigation

JUMO diraVIEW 132 (landscape format 48 x 24 mm, 1 x analogue input, 1 x relay, 1 x DI, 1 x DI / DO)

Article number: 802132
Our service hotline – We are here for you 📞 +49 (0) 5121 7609 99

Product information "JUMO diraVIEW 132 (landscape format 48 x 24 mm, 1 x analogue input, 1 x relay, 1 x DI, 1 x DI / DO) "

JUMO diraVIEW 132 – Digital display (Type: 701510/8-0000-23/000)

In this version, the device features a universal analog input that can process different signal types. In addition, two digital inputs are available, one of which can alternatively be used as a logic output.

The JUMO diraVIEW 132 is a compact digital display in landscape format 48 × 24 mm for displaying and monitoring process variables such as temperature, pressure or analog signals. Despite its small design, the device offers a wide range of functions for industrial applications.

The display of measured values and parameters is clearly presented via two 18-segment LCD displays. Additional display elements provide information about switching states and active functions.

Operation is carried out via a membrane keypad with four buttons. Thanks to protection class IP65, the device is also suitable for demanding environmental conditions.

Equipment of this device variant

  • 1 universal analog input
  • 2 digital inputs (digital input 1 can alternatively be used as a logic output)
  • 1 relay output (normally open contact)
  • 1 logic output 0/14 V (alternative to digital input 1)
  • Power supply: AC 110–240 V (+10 / -15 %), 48–63 Hz
  • Display via 2 × 18-segment LCD
  • Compact format: 48 × 24 mm (landscape format)

Functions and possibilities

The diraVIEW 132 combines display, monitoring and simple control functions in a compact device:

  • Min/max value storage for continuous evaluation
  • Hold function for freezing measured values
  • Tare function, also suitable for weighing applications
  • Timer function for time-dependent processes
  • Monitoring of up to 4 limit values with extensive alarm functions

In addition, digital control signals can be flexibly processed and linked.

Signal processing & flexibility

All signals are internally managed via selectors, enabling flexible assignment of inputs and outputs. This allows the device to be individually adapted to different applications.

Interfaces & configuration

The device features a USB device interface for connection to a PC. Parameterization is carried out via the setup program, with which:

  • settings can be created and transferred
  • data can be read out and saved
  • wiring diagrams can be generated automatically

During configuration, the power supply is provided directly via USB.

Advantages and special features

  • universal analog input for flexible applications
  • compact design for confined installation spaces
  • combination of display, monitoring and control
  • versatile functions such as timer, min/max and tare
  • robust design with protection class IP65

Possible application areas

  • monitoring temperature values in heating and cooling processes
  • use in industrial systems with available mains voltage
  • monitoring of pressure or flow values in process systems
  • integration into machine controls for displaying process data
  • limit value monitoring with direct switching via relay
  • use in production environments with continuous power supply
  • visualization of measured values in control cabinets

Detailed overview of the functionalities of the JUMO diraVIEW 132

Signal assignment via selectors

The input signals as well as all internal signals are available in so-called selectors (analog selector, digital selector) for further use within the device. The control signals for the outputs are also assigned via selectors, enabling flexible assignment of signals and functions.

Interfaces

The device features a USB device interface (Micro-B socket on the rear), specifically intended for connection to a PC for use with the setup program. During configuration, the device is powered via this USB interface, so no mains supply is required.

Optionally, an RS485 interface is available for communication with a Modbus master (Modbus RTU mode). The master can transmit up to two analog values and two binary values to the device, which are then used as external input signals. In addition, two analog markers and two digital markers (binary) are available. An optional Ethernet interface is also available, supporting Modbus TCP and Modbus RTU/ASCII over TCP. The same parameters and process values can be transmitted via this interface as via the RS485 interface.

Power supply

Two power supply variants are available:

  • AC 110 to 240 V
  • AC/DC 20 to 30 V

each 48 to 63 Hz

Electrical connection

Simple and time-saving connection using practical spring-loaded terminals (push-in technology)

Min/max function

Using the min/max function, the lowest and highest measured values are stored and continuously updated. These values can be displayed separately or alternately with the current value. A binary signal allows the stored values to be reset to the current measured value.

Hold function

The hold function freezes the display value, meaning it remains displayed as long as the controlling binary signal is active.

Tare function

The tare function allows the display value to be set to zero, controlled by a binary signal (e.g. in weighing applications). The currently displayed value is added to the tare value each time. Another binary signal can reset the tare value to zero so that the current value is displayed again.

Limit value monitoring

The device features four limit value monitors, each with eight configurable alarm functions. Any analog signal from a selector can be selected for monitoring. The limit values can either be absolute values or dependent on another analog signal. Various special functions are available such as:

  • switch-on/off delay
  • wiper function
  • alarm suppression during startup or parameter changes
  • alarm latching
  • latching with acknowledgement

These extensive functions enable flexible and precise implementation of alarm and limit value functions.

Digital control signals

This function allows configuration of up to 4 digital control signals. The control signal can be formed by AND/OR/XOR linking of up to three selectable binary signals, or a single binary signal can be used as an input signal and output as a pulse, delayed signal, wiper signal or edge-triggered signal. In the latter case, the rising or falling edge of the binary signal is detected and the output signal is activated for the duration of a sampling interval. The output signal can be inverted in all cases.

Timer

After activation, the timer generates an invertible signal for the defined runtime. The timer can also be started after a lead time has elapsed or a tolerance limit has been reached. After the timer expires, a timer end signal can be generated, which is either time-limited or requires acknowledgement. These timer functions enable a wide range of time-dependent processes.

Service counter

The service counter can either count the number of switching operations of a binary signal or measure its operating time. Once the defined limit value is reached, a binary signal is activated that must be acknowledged. In addition, an operating hours counter records the device runtime.

Mathematics and logic function

The optional mathematics and logic function (type extension) allows analog or binary values to be linked. Up to four freely configurable formulas can be created using the setup program. The results are then available in the analog or digital selector for further use.

User-defined level

The user-defined level provides space for up to 16 editable configuration parameters. These parameters can be individually selected in the setup program.

Setup program

The setup program allows data records to be created, edited, transferred to the device and read from it. The data can be saved and printed. It also enables easy creation and printing of wiring diagrams showing the current terminal assignment.

Startup: The startup function allows recording of process variables during commissioning for up to 24 hours. The recorded diagrams are available on the PC and can be used for documentation purposes.

Online data: Current process values of the device are displayed in a separate window.

Custom linearization

Individual linearization allows the use of sensor signals with special characteristics. Programming is carried out in the setup program either via a value table with up to 40 value pairs or via a formula (4th order polynomial). The device supports 2 custom linearizations.

Structured text

With the "Structured Text" option (type extension), users can develop individual applications. These are created using the ST editor within the setup program and use the PLC programming language "Structured Text". After completion, the application is transferred to the device and executed continuously. Online debugger functions are available for troubleshooting and testing.

Using ST code, up to 10 stored text messages can be displayed depending on the application.

Dimensions

Height 6,7 cm
Length 10,6 cm
Width 7,6 cm

Weight

Weight 174 g

Other attributes

Country of origin DE
Customs tariff number 90303370
Format 48 x 24 mm
Spannungsversorgung AC 110 bis 240 V + 10/-15% , 48 bis 63Hz
Technical data:

Analog Input

Thermocouples

Designation

Typ

Norm

ITS

Measuring range

Accuracy

Fe-CuNi

„L“

DIN 43710 (1985)

IPTS-68

-200 to +900 C

0,25 %

Fe-CuNi

„J“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-210 to +1200 °C

 0,25 % off -100 °C

Cu-CuNi

„U“

DIN 43710 (1985)

IPTS-68

-200 to +600 °C

0,25 % off -100 °C

Cu-CuNi

„T“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-270 to +400 °C

 0,25 % off -150 °C

NiCr-Ni

„K“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-270 to +1300 °C

 0,25 % off -80 °C

NiCr-CuNi

„E“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-270 to +1000 °C

 0,25 % off -80 °C

NiCrSi-NiSi

„N“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-270 to +1300 °C

0,25 % off -80 °C

Pt10Rh-Pt

„S“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-50 to +1768 °C

0,4 % off 20 °C

Pt13Rh-Pt

„R“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-50 to +1768 °C

0,25 % off 50 °C

Pt30Rh-Pt6Rh

„B“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

-50 to +1820 °C

0,25 % off 400 °C

W5Re-W26Re

„C“

DIN EN 60584-1:2014

IEC 60584-1:2013

ITS-90

0 to 2315 °C

0,25 % off 500 °C

W3Re-W25Re

„D“

ASTM E1751M-15

ITS-90

0 to 2315 °C

0,25 % off 500 °C

W5Re-W20Re

„A1“

GOST R 8.585-2001

ITS-90

0 to 2500 °C

0,25 % off 500 °C

Chromel®-Copel

„L“

GOST R 8.585-2001

ITS-90

-200 to +800 °C

 0,25 % off -80 °C

Chromel®-Alumel®

„K“

GOST R 8.585-2001

ITS-90

-270 to +1300 °C

 0,25 % off -80 °C

a  Accuracy refers to the measurement range.

 

Ambient temperature influence

100 ppm/K

Comparison agency

internal or external (constant)

Comparison point temperature (ex- tern)

0 to 100 °C (adjustable)

Sampling cycle

150 ms

Eingangsfilter

2nd order digital filter; Filter constant adjustable from 0 to 100.0 s

 

Resistance thermometer

Designation

Norm

ITS

Connection type

Measuring range

Accuracy

Measuring current

Pt100

DIN EN 60751:2009

IEC 60751:2008

ITS-90

2-Ladder

-200 to +850 °C

0,2 %

500 A

3- Ladder

-200 to +850 °C

0,1 %

500 A

Pt1000

DIN EN 60751:2009

IEC 60751:2008

ITS-90

2-/3- Ladder

-200 to +850 °C

0,1 %

50 A

Pt100

GOST 6651-2009 A.2

ITS-90

2- Ladder

-200 to +850 °C

0,2 %

500 A

3- Ladder

-200 to +850 °C

0,1 %

500 A

KTY

 

 

2- Ladder

-53 to +153 °C

2,0 %

50 A

a  Accuracy refers to the measurement range.

 

Ambient temperature influence

50 ppm/K

Sensor Line Resistance

max. 30 je Line

Sampling cycle

150 ms

Speeds

2nd order digital filter; Filter constant adjustable from 0 to 100.0 s

 

Resistance Potentiometer/WFG and Resistance/Potentiometer

 

Designation

Measuring range

Accuracya

Measuring current

Widerstandspotenziometer/WFG

0 bis 4000

0,1 %

50 A

Widerstand/Poti

0 to 400

0 to 4000

0,1 %

0,1 %

500 A

50 A

a Accuracy refers to the maximum measurement range. At small measuring spans, the linearization accuracy is reduced.

 

Ambient temperature influence

100 ppm/K

Anschlussart

 

Resistance Potentiometer/

Three-wire circuit

WFG

 

Widerstand/Poti

Two-/three-wire circuit

Sensor Line Resistance

max. 30 per line

Sampling cycle

150 ms

Speeds

2nd order digital filter; Filter constant adjustable from 0 to 100.0 s

Voltage, current (unit signals)

 

Designation

Measuring range

Accuracy

Input resistance or load voltage

Voltage

0 to 10 V

0,1 %

>  500 k

2 to 10 V

0,1 %

>  500 k

Current

4 to 20 mA

0,1 %

2,5 V

0 to 20 mA

0,1 %

2,5 V

a Accuracy refers to the maximum measurement range. At small measuring spans, the linearization accuracy is reduced.

 

Ambient temperature influence

100 ppm/K

Measuring range under/exceeding

according to NAMUR recommendation NE 43 (only current input 4 to 20 mA)

Sampling cycle

150 ms

Speeds

2nd order digital filter; Filter constant adjustable from 0 to 100.0 s

Measuring Circuit Monitoring

The behavior of the device in the event of a fault is configurable.

 

Transmitter

Measuring range below

Exceeding the measuring range

Short circuit (sensor/line)

Bruch (Fühler/Lei- tung)

Reverse polarity

Widerstandsthermo- meter

++

++

++

++

---

Widerstand/Poti

---

++

---

++

---

Widerstandspotenzio- meter/WFG

---

++

(+)a

(+)b

---

Thermoelement

++

++

---

++

(+)c

Strom 0 to 20 mA

---

++

---

---

---

Strom 4 to 20 mA

++

++

++

++

++

Spannung 0 to 10 V

---

++

---

---

++

Spannung 2 to 10 V

++

++

++

++

++

++ = is detected                                                                   --- = is not recognized                                                        (+) = is conditionally recognized

a  is not recognized in all combinations

b  Break in the measurement current path is not detected

c  depending on the set characteristic curve

 

Digital Inputs

 

Input for potential-free contact

Function

 

Sampling cycle

 

Contact closed: Input is active (RON < 1 kΩ)

Contact open: Receipt is inactive (ROFF > 50 kΩ)

150 ms

Analogoutput

 

Voltage

Ausgangssignal Lastwiderstand

 

DC 0(2) to

Output Signal Load Resistance 10 V

> 500

Current

Output Signal Load Resistance

 

DC 0(4) bis 20 mA

< 450

Accuracy

0,5 %

Ambient temperature influence

150 ppm/K

Digitalausgänge

 

Relay (NO contact)

Switching capacity contact life

 

max. 3 A bei AC 230 V or DC 30 V, ohmsche Last

150.000 Circuits at Rated Load

350.000 Circuits at 1 A

Relays (NO contacts) with longer contact life

Schaltleistung Kontaktlebensdauer

 

 

max. 3 A bei AC 230 V, ohmsche Last

300.000 Schaltungen bei Nennlast

1.500.000 Schaltungen bei 1 A

Logic Output

Output

Strom

 

DC 0/14 V 15 %

max. 20 mA per output (at nominal voltage 14 V)

PhotoMOS®-Relaisa

Switching capacity

 

max. 200 mA at AC 30 V or DC 45 V; not short-circuit proof

a PhotoMOS is a registered trademark of Panasonic Corporation.

 

Interfaces

 

USB-Device

 

Plug Type

Micro-B (Buchse)

Standard

Low-Speed, Full-Speed

Max. cable length

5 m

RS485

 

Baudrate

9600, 19200, 38400, 115200

Data format

8/1n, 8/1e, 8/1o, 8/2n

Protocol

Modbus-RTU as Slave

Ethernet

 

Plug Type

RJ45 (Buchse)

Übertragungsrate

10 Mbit/s, 100 Mbit/s

Protocol

TCP/IP, DHCP; Modbus-TCP, Modbus-RTU/ASCII über TCP, als Slave

 

Display

 

18-segment LCD displays

Digit height

obere Anzeige:

bottom display:

Typ 701510 (Format 132)

7,2 mm

3,8 mm

Typ 701511 (Format 116)

12,3 mm

5,9 mm

Typ 701512 (Format 108H)

11,5 mm

8,5 mm

Typ 701513 (Format 108Q)

16,5 mm

9 mm

Typ 701514 (Format 104)

24,8 mm

12 mm

Color

top display: white; Bottom display: green

Digits incl. decimal places

top display: 4; bottom display: 4 (5 for type 701510, 8 for type 701511)

Decimal places

0, 1, 2, 3 or automatically (configurable)

 

Pixel matrix LCD display (701512, 701513, and 701514 types only)

Pixel Fields

 

Typ 701512 (Format 108H)

2 rows of 9 pixel fields each

Typ 701513 (Format 108Q)

2 rows of 8 pixel fields each

Typ 701514 (Format 104)

2 rows of 11 pixel fields each

Pixelanzahl is Feld

8 x 5

Color

weiß

Electric Dating

 

Spannungsversorgung Variante 1

Variante 2

(see nameplate)

AC 110 to 240 V +10/-15 %, 48 to 63 Hz

AC/DC 20 to 30V, 48 to 63Hz

Electrical safety

according to DIN EN 61010, Part 1; Overvoltage category II up to 300 V mains voltage, contamination grade 2

Class

I with internal separation to SELV

Power consumption

at AC 110 to 240 V:

for AC/DC 20 to 30 V:

Typ 701510 (Format 132)

max. 3,5 W

max. 3,0 W

Typ 701511 (Format 116)

max. 4,1 W

max. 3,7 W

Typen 701512, 701513

(Formate 108H, 108Q)

max. 5,8 W

max. 5,7 W

Typ 701514 (Format 104)

max. 6,6 W

max. 6,7 W

Electrical connection

on the back via spring-loaded clamps (push-in technology)

Conductor cross-section

 

Wire or stranded wire

min. 0,2 mm2, max. 1,5 mm2

(without ferrule)

 

Stranded wire with ferrule

without plastic collar: min. 0,2 mm2, max. 1,5 mm2

 

mit Kunststoffkragen: min. 0,2 mm2, max. 0,75 mm2

Stripping length

8 mm

Umwelteinflüsse

 

Ambient temperature range

Storage

Operation

 

-30 to +70 °C

-10 to +55 °C

Installation height

max. 2000 m above NN

Climatic environmental conditions Climate resistance

Storage

according to DIN EN 60721-3 with extended temperature range

90 % relative humidity without condensation after class 1K2

Operation

after class 3K3

 

Mechanical environmental conditions Storage

Transport

Operation

according to DIN EN 60721-3

according to class 1M2

by class 2M2

according to class 3M3

Electromagnetic compatibility (EMV) Emission

Stability

according to DIN EN 61326-1

Class A - for industrial use only - Industry Requirement

Gehäuse

 

Housing type

Plastic enclosures for panel installation in accordance with DIN IEC 61554 (use indoors))

Cabinet front

made of plastic with membrane keypad

Panel thickness

1 to 10 mm

Housing Mounting

in the control panel using the supplied mounting frame or the two fastening elements

Usage position

Any a

Protection

according to DIN EN 60529, front IP65, rear IP20

Gewicht

 

Typ 701510 (Format 132)

max. 85 g

Typ 701511 (Format 116)

max. 120 g

Typ 701512 (Format 108H)

max. 160 g

Typ 701513 (Format 108Q)

max. 160 g

Typ 701514 (Format 104)

max. 220 g

a The maximum permissible ambient temperature only applies to installation with vertical orientation of the display.

 

Approvals and test marks

 

Mark

Checkpoint

Certificates/Test Numbers

Test basis

Applies to

c UL us

Underwriters Laboratories

E201387

UL 61010-1 (3. Ed.),

CAN/CSA-22.2 No. 61010-1

(3. Ed.)

all versions

DNV GL

DNV GL

TAA00001B3

Class Guideline DNVGL-CG-0339

Typ 701511 (DC 20 bis 30 V)

and Type 701514 (AC 110 to 240 V), without Ethernet interface, panel mounting

BUREAU VERITAS

Bureau Veritas

53627/A0 BV

Bureau Veritas Rules for the Classification of Steel Ships

The device has approval if the relevant test mark is shown on the device.