JUMO hydroTRANS S20
€209.90*
Please log in to receive your conditions.
Available in 28 days, delivery time 1-2 days
(Login for quotation) The entered number of pieces will be taken into account when creating the quotation.
Product information "JUMO hydroTRANS S20 "
Combined transmitter for humidity and temperature measurement from the JUMO brand, hydroTRANS S20 variant
JUMO hydroTRANS S20 – Humidity and temperature transmitter (wall mounting) Type: 907042/11-0-15-009/000
This version of the hydroTRANS from JUMO is a wall-mounted humidity and temperature transmitter for monitoring indoor air quality. With a configurable output signal and robust multisensor system, it is suitable for air conditioning, ventilation, and building technology as well as storage and monitoring applications.
The JUMO hydroTRANS S20 is therefore a combined transmitter for measuring relative humidity and temperature in indoor areas as well as protected outdoor environments. It is suitable for the continuous monitoring of indoor air quality in technical systems, buildings, and storage environments.
Technical data
- Basic type extension: RH-T
- Version: Standard
- Measuring range: 0 … 100 % RH / -40 … +80 °C
- Measured parameters: relative humidity, temperature
- Output: 4–20 mA / 0–10 V (combined output configurable)
Advantages and technical features of the JUMO hydroTRANS S20
- Combined measurement of humidity and temperature in one device
- Wide measuring range up to 100 % RH and -40 to +80 °C
- Flexible combined output (4–20 mA or 0–10 V configurable)
- Easy wall mounting for quick installation
- Suitable for indoor areas and protected outdoor environments
- Robust design for continuous indoor air quality monitoring
The measuring range covers 0 to 100 % relative humidity as well as temperatures from -40 to +80 °C. The measured values can be output via a configurable combined output (4–20 mA or 0–10 V), allowing flexible adaptation to different control and regulation concepts.
This wall-mounted version is designed for easy installation and enables direct mounting on walls or in climate-relevant areas. This makes the device particularly suitable for applications where quick integration without complex installation steps is required.
The multisensor technology enables simultaneous acquisition of humidity and temperature values. Optionally, the transmitter can be equipped with a plastic sinter filter that additionally protects the sensor from dust and particles, thereby supporting the stability of the measured values.
Typical areas of application
- Climate monitoring in buildings
- Ventilation and air conditioning systems
- Building management systems
- Storage rooms and archives
Dimensions
| Height | 7 cm |
|---|---|
| Length | 19 cm |
| Width | 12 cm |
Weight
| Weight | 0,3 kg |
|---|
Other attributes
| Ausgang | 4...20 mA / 0...10 V (Kombiausgang konfiguriert) |
|---|---|
| Customs tariff number | 90258040 |
| Messbereich (Temperatur & relative Feuchte) | 0...100% rF / -40°C...+80°C |
| Messparameter | Relative Feuchte, Temperatur |
| Requirements | standard / specification |
|---|---|
| The device must be connected to a circuit that meets the requirements for “energy-limited circuits”. | DIN EN IEC 61010-1:2020 |
| Power supply | DC 24 V, -33 % / +33 %, SELV, PELV |
|---|---|
| power consumption | ≤ 2,4 W |
| overvoltage category | II |
| Degree of contamination | 2 |
| protection class | DIN EN 61140, Class III (safety extra-low voltage) |
| electrical connection | |
| connection elements | spring-loaded terminal |
| connecting cable |
|
| stripping length |
|
| temperature resistance | ≥ 80 °C |
| power supply | DC 24 V, -58 % / +33 %, SELV, PELV |
|---|---|
| power consumption | ≤ 2,4 W |
| overvoltage category | II |
| pollution degree | 2 |
| protection class | DIN EN 61140, class III (safety extra-low voltage) |
| electrical connection | |
| connection elements | spring-cage terminal |
| connecting cable |
|
| stripping length |
|
| temperature resistance | ≥ 80 °C |
| property | value |
|---|---|
| supply voltage | DC 18 to 30 V, PELV |
| current draw | ≤ 100 mA |
| power consumption | ≤ 1,8 W |
| overvoltage category | II |
| pollution degree | 2 |
| protection class | DIN EN 61140, class III (Ssafety extra-low voltage) |
| PoDL-class | class 11, IEEE 802.3cg |
| PoDL classification | SCCP- or Forced-Mode |
| electrical connection | |
| connection element | M12 connector |
| M12 connector | IEC 63171-5 |
| design | 2-pin, shielded |
| ingress protection (IP rating) | IP67 |
| connecting cable | IEC 61156-13, IEC 61156-14 |
| cable design | 2-core, copper, shielded |
| bandwidth | ≥ 20 MHz |
| cable length | ≤ 500 m (AWG22 at DC 24 V) |
| DC loop resistance | < 59 Ω |
| temperature resistance | ≥ 80 °C |
| property | value |
|---|---|
| measuring range |
|
| measurement accuracy |
|
| sampling rate | 1 s |
| Propertyt | Value |
|---|---|
| measuring range |
|
| measurement accuracy |
|
| sampling rate | 1 s |
| property | Value |
|---|---|
| General information | |
| Availability |
Optional for devices with an analogue output and RS485, factory-set for devices with SPE |
| measurement range | 400 to 10 000 ppm |
| measurement accuracy & reference conditions | |
| measurement accuracy | ±(50 ppm + 5 % of the measured value) |
| ambient temperature | 25 °C |
| air pressure | 1013 hPa |
| humidity | 50 % RH |
| measuring range | 400 to 1 000 ppm |
| sampling rate | 30 s |
| property | Value |
|---|---|
| current output | |
| signal range | 4 to 20 mA |
| output signal limits | 0 to 22 mA |
| measurement accuracy | ≤ ±0,05 % relative to the end of the signal range (20 mA) |
| temperature influence | ±50 ppm/K |
| load influence | ≤ ±0,02 % per 100 Ω |
| load | ≤ 500 Ω |
| property | Value |
|---|---|
| voltage output | |
| signal range | 0 to 10 V |
| output signal limits | 0 to 11 V |
| accuracy | ≤ ±0,05 % relative to the end of the signal range (10 V) |
| temperature influence | 50 ppm/K |
| load influence | ≤ ±15 mV |
| load | ≥ 10 kΩ |
| property | specification |
|---|---|
| function | transfer of configuration data and device information |
| communication | via end device and setup software |
| transmission standard | USB 2.0 |
| connector type | Micro-B |
| current consumption | ≤ 500 mA |
| cable length | ≤ 5 m |
| property | specification |
|---|---|
| function | Transfer of process data, configuration data and device information |
| communication | via Modbus master |
| galvanic isolation | functional |
| data transmission | serial |
| transmission protocol | Modbus RTU |
| data format |
|
| data transmission rate |
|
| minimum response time | 0 to 500 ms |
| device address | 1 to 254 |
| property | specification |
|---|---|
| function | Transmission of process data, configuration data and device information, power supply via PoDL |
| communication | Via the terminal and the JUMO Cloud, Modbus master |
| SPE standard | 10BASE-T1L |
| transmission protocol | Modbus TCP, integrated JUMO Cloud gateway |
| data transmission rate | 10 Mbit/s |
| property | specification |
|---|---|
| Type | TFT-Display |
| Size |
Display Area: 35,04 mm × 28,03 mm Screen diagonal: 1,77″ |
| resolution | 128 × 160 px RGB |
| brightness | 11 Steps (configurable) |
| property | specification |
|---|---|
| Permissible ambient temperature |
Permissible ambient temperature: -40 to +80 °C With CO₂-Modul: -10 to +60 °C With display: -20 to +60 °C |
| Permissible storage temperature |
Permissible storage temperature: -40 to +80 °C With CO₂ module: -30 to +70 °C With display unit: -30 to +60 °C |
| Degree of protection | IP65 (DIN EN 60529) |
| Max. installation altitude | 5300 m above sea level |
| Climatic conditions / climatic class | DIN EN IEC 60721-3-3 / 3K24 |
| Relative humidity | ≤ 100 % (95 % with CO₂ module), non-condensing |
| Electromagnetic compatibility (EMC) | DIN EN IEC 61326-2-3:2022 |
| EMC – Emissions | Class Ba |
| EMC – Immunity | Industrial requirements |
| vibrationb |
vibration: DIN EN 60068-2-6 Deflection: 0,15 mm from 10 to 58,1 Hz Acceleration: 20 m/s² from 58,1 to 150 Hz |
| Shockb |
Shock resistance according to DIN EN 60068-2-27 Peak acceleration: 150 m/s² Shock duration: 11 ms |
|
a The product is suitable for industrial use as well as for domestic and small business use. b The CO₂ module is sensitive to vibrations. Due to its design, vibrations may affect the measurement result. |
|
| property | specification |
|---|---|
| Materials of housing / display cover | PC / PMMA |
| Weight | Approx. 200 g |