JUMO diraVIEW 105 (96 x 96 mm, 1 analog input, 2 relays, 1 digital input, 1 digital input/output)

Article number: 802138
Our service hotline – We are here for you 📞 +49 (0) 5121 7609 99

Product information "JUMO diraVIEW 105 (96 x 96 mm, 1 analog input, 2 relays, 1 digital input, 1 digital input/output)"

JUMO diraVIEW 108 - Digital indicator

Typ: 701514/8-0000-23/000

  • Version: Standard with factory settings
  • Power supply: AC 110-240 V +10/-15%, 48 to 63 Hz
  • Option 1-4: not assigned
  • Extra code: without
  •  1 analogue input
  •  2 digital inputs (digital input 1 as an alternative to logic output)
  •  1 relay (normally open contact)
  •  1 logic output 0/14 V (alternative to digital input 1)
  •  Display and storage of min/max values
  •  Tare function
  •  Hold function
  •  Tare function for weighing applications
  •  Customised linearisation with the option of defining up to 40 value pairs or a polynomial
  •  Timer function
  •  Monitoring of 4 limit values
  •  Customised user levels
  •  Optional customised application using structured text (ST code)
  •  Optional maths and logic function
  •  Simple installation thanks to push-in technology
  •  Optional analogue output
  •  Optional RS485 or Ethernet interface
  •  Additional analogue and digital inputs via the interface

This digital indicator consists of five freely configurable and universally applicable devices in different DIN formats for displaying temperature, pressure and other process variables. The process variables and parameters are displayed on two 18-segment LCD displays. Types 701512, 701513 and 701514 are also equipped with a pixel matrix LCD display for displaying text. In addition, all devices have separate display elements for the switching positions of the outputs and the timer. They are operated via a membrane keypad with four buttons and are suitable for use in harsh environmental conditions thanks to their high IP65 protection rating.

Inputs and outputs

Each device type is equipped with a universal analogue input that is suitable for resistance thermometers, thermocouples, current, voltage, resistance transmitters and resistance/potentiometers. In addition, each device has a digital input, a switchable digital input/output.

With the exception of type 701510, which has one relay output (normally open contact) as standard, all other types have two relay outputs (normally open contact). The digital inputs are designed for connection with a potential-free contact. The digital output provides a logic signal from 0 to 14 V. Furthermore, additional optional

  •  Relay outputs (normally open contact)
  •  Logic outputs (0 to 14 V)
  •  PhotoMOS® relay outputs
  •  Analogue output (0 to 10V / 0 to 20 mA)

are available.
Certain inputs and outputs cannot be used simultaneously (see notes in the connection diagram)
Signal assignment via selectors
The input signals and all internal signals are available in so-called selectors (analogue selector, digital selector) for further use in the device. The control signals for the outputs are also assigned via selectors, which enables flexible assignment of signals and functions.

Interfaces
The device has a USB device interface (Micro-B socket on the rear), which is specially designed for connection to a PC for the setup programme. During configuration, the device is supplied with power via this USB interface so that no mains supply is required.
An optional RS485 interface is available, which is intended for communication with a Modbus master (Modbus RTU operating mode). The master can transmit up to two analogue values and two binary values to the device, which are used there as external input signals. In addition, two analogue flags and two digital flags (binary) are available. An Ethernet interface is also available as an option, which supports the Modbus TCP and Modbus RTU/ASCII operating modes via TCP. The same parameters and process values can be transmitted via this interface as via the RS485 interface.

Power supply
Two power supply variants are available:

  •  AC110 to 240 V
  •  AC/DC 20 to 30 V

48 to 63 Hz in each case

Electrical connection
Simple and time-saving connection using practical spring-loaded terminals (push-in technology)

Min-max function
Using the min-max function, the lowest and highest measured values are saved and continuously updated. It is possible to display these values separately or alternately with the current measured value. A binary signal makes it possible to reset the stored values and return them to the current measured value.

Hold function
The hold function "freezes" the value of the indicator, which means that this value is displayed for as long as the controlling binary signal is active.

Tare function
The tare function makes it possible to set the value of the indicator to zero, controlled by a binary signal (for weighing applications). The currently displayed value is added to the tare value each time. Another binary signal can be used to reset the tare value to zero so that the current value appears on the display again.

Limit value monitoring
The device has four limit value monitors, each with eight configurable alarm functions. Any analogue signal can be selected from a selector for monitoring. The limit values can either be absolute values or depend on another analogue signal. Various special functions are available, such as

  •  On/off delay
  •  Wiper function
  •  Alarm suppression during the switch-on phase or in the event of parameter changes
  •  Alarm latching
  •  Latching with acknowledgement

available.
These extensive functions enable flexible and precise realisation of alarm and limit value functions.

Digital control signals
This function enables the configuration of up to 4 digital control signals. The control signal is either formed by an AND/OR/XOR combination of up to three selectable binary signals or a single binary signal is used as an input signal and can be output as a pulsed signal, delayed signal, wiper signal or edge-triggered signal. In the latter case, the rising or falling edge of the binary signal is determined and the output signal is activated for the duration of a sampling interval. The output signal can be inverted in all these cases.

Timer
Once the timer is activated, an invertible signal is generated for the specified timer runtime. The timer can also be started after a lead time has elapsed or a tolerance limit has been reached. After the timer has elapsed, a timer end signal can be generated that is either time-limited or requires acknowledgement. These timer functions enable a wide range of time-dependent processes.

Service counter
The service counter can either count the number of switching operations of a binary signal or measure its switch-on duration. As soon as the adjustable limit value is reached, a binary signal is activated that must be acknowledged. An operating hours counter is also available, which records the operating time of the device.

Maths and logic function
The optional maths and logic function (extra code) can be used to link analogue or binary values. Up to four freely configurable maths or logic formulas can be created using the setup program. The results are then available for further use in the analogue or digital selector.

Individual user level
The individual user level offers space for up to 16 editable configuration parameters. These parameters can be selected individually in the setup programme.

Setup programme
With the setup programme, data records can be created, edited, transferred to the device and read out from there. The data can be saved and printed out. The programme also allows the user to easily create and print out a connection diagram showing the current terminal assignment of the device.
Startup: The startup function enables the recording of process variables during commissioning for a maximum of 24 hours. The recorded diagrams are available on the PC and can be used for system documentation, for example.
Online data: The current process variables of the device are displayed in a separate window.

Customer-specific linearisation
Individual linearisation according to customer requirements also makes it possible to use sensor signals with special characteristics. Programming is carried out in the setup program either using your value table with up to 40 value pairs or using a formula (4th order polynomial). The device supports 2 customer-specific linearisations.

Structured text
The "Structured text" option (extra code) allows the user to develop a customised application. This application is created using the ST editor, which is part of the setup programme, and uses the "Structured text" PLC programming language. Once completed, the application is transferred to the device and executed continuously. Online debugger functions are available in the ST editor for troubleshooting and testing.
With the help of the ST code, it is possible to display up to 10 stored text messages depending on the application.

Dimensions

Height 8,6 cm
Length 10,6 cm
Width 9,8 cm

Weight

Weight 286 g

Other attributes

Country of origin DE
Customs tariff number 90303370
Format 96 x 96 mm
Spannungsversorgung AC 110 bis 240 V + 10/-15% , 48 bis 63Hz
Technical data:
Technical Specifications – Analogue Input for Thermocouples
Designation Type standard ITS Measuring range Accuracya
Fe-CuNi „L“ DIN 43710 (1985) IPTS-68 -200 to +900 °C ≤ 0,25 %
Fe-CuNi „J“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -210 to +1200 °C ≤ 0,25 % from -100 °C
Cu-CuNi „U“ DIN 43710 (1985) IPTS-68 -200 to +600 °C ≤ 0,25 % from -100 °C
Cu-CuNi „T“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +400 °C ≤ 0,25 % from -150 °C
NiCr-Ni „K“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +1300 °C ≤ 0,25 % from -80 °C
NiCr-CuNi „E“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +1000 °C ≤ 0,25 % from -80 °C
NiCrSi-NiSi „N“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +1300 °C ≤ 0,25 % from -80 °C
Pt10Rh-Pt „S“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -50 to +1768 °C ≤ 0,4 % from 20 °C
Pt13Rh-Pt „R“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -50 to +1768 °C ≤ 0,25 % from 50 °C
Pt30Rh-Pt6Rh „B“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -50 to +1820 °C ≤ 0,25 % from 400 °C
W5Re-W26Re „C“ DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 0 to 2315 °C ≤ 0,25 % from 500 °C
W3Re-W25Re „D“ ASTM E1751M-15 ITS-90 0 to 2315 °C ≤ 0,25 % from 500 °C
W5Re-W20Re „A1“ GOST R 8.585-2001 ITS-90 0 to 2500 °C ≤ 0,25 % from 500 °C
Chromel®-Copel „L“ GOST R 8.585-2001 ITS-90 -200 to +800 °C ≤ 0,25 % from -80 °C
Chromel®-Alumel® „K“ GOST R 8.585-2001 ITS-90 -270 to +1300 °C ≤ 0,25 % from -80 °C
a The accuracy applies to the measurement range.
Technical additional data – thermocouples
Parameter Description
Effect of ambient temperature ≤ 100 ppm/K
Comparison site internal or external (constant)
Reference point temperature (external) 0 to 100 °C (adjustable)
sampling cycle 150 ms
Input filter second-order digital filter;
Filter constant adjustable from 0 to 100.0 s
Technical specifications – Resistance temperature sensors
Designation standard ITS Connection type Measuring range Accuracya Measuring current
Pt100 DIN EN 60751:2009
IEC 60751:2008
ITS-90 2-wire connection -200 to +850 °C ≤ 0,2 % 500 µA
3-wire connection -200 to +850 °C ≤ 0,1 % 500 µA
Pt1000 DIN EN 60751:2009
IEC 60751:2008
ITS-90 2-/3-wire connection -200 to +850 °C ≤ 0,1 % 50 µA
Pt100 GOST 6651-2009 A.2 ITS-90 2-wire connection -200 to +850 °C ≤ 0,2 % 500 µA
3-wire connection -200 to +850 °C ≤ 0,1 % 500 µA
KTY 2-wire connection -53 to +153 °C ≤ 2,0 % 50 µA
a The accuracy applies to the measurement range.
Technical specifications – Resistance temperature sensors
Parameter Description
Effect of ambient temperature ≤ 50 ppm/K
Sensor lead resistance max. 30 Ω per line
sampling cycle 150 ms
Input filter second-order digital filter;
Filter constant adjustable from 0 to 100.0 s
Technical specifications – Resistor potentiometer / Resistor / Potentiometer
Designation Measuring range Accuracya Measuring current
resistance potentiometer / WFG 0 to 4000 Ω ≤ 0,1 % 50 µA
Resistor / potentiometer 0 to 400 Ω ≤ 0,1 % 500 µA
0 to 4000 Ω ≤ 0,1 % 50 µA
a The accuracy refers to the maximum measuring range. For small measuring ranges, the linearity accuracy is reduced.
Technical data – resistance potentiometer / resistor / potentiometer
Parameter Description
Effect of ambient temperature ≤ 100 ppm/K
Connection type Resistance potentiometer / WFG: three-wire connection
Resistor / potentiometer: two-/three-wire connection
Sensor lead resistance max. 30 Ω per line
sampling cycle 150 ms
Input filter second-order digital filter;
Filter constant adjustable from 0 to 100.0 s
Technical specifications – Voltage and current (standard signals)
Description Measurement range accuracya Input resistance or load voltage
Voltage 0 to 10 V ≤ 0,1 % > 500 kΩ
2 to 10 V ≤ 0,1 % > 500 kΩ
Electricity 4 to 20 mA ≤ 0,1 % < 2,5 V
0 to 20 mA ≤ 0,1 % < 2,5 V
a The accuracy refers to the maximum measuring range. For small measuring ranges, the linearity accuracy is reduced.
Technical additional data – voltage, current (standard signals)
Parameter Description
The effect of ambient temperature ≤ 100 ppm/K
Measurement range under/over-range in accordance with NAMUR recommendation NE 43
(4–20 mA current input only)
sampling cycle 150 ms
Input filter second-order digital filter;
Filter constant adjustable from 0 to 100.0 s
Circuit monitoring – behaviour in the event of a fault
measuring transducer Value below the measurement range Exceeding the measurement range Short circuit (sensor/cable) Break (sensor/cable) Reverse polarity
Resistance thermometer ++ ++ ++ ++ ---
resistor / potentiometer --- ++ --- ++ ---
Potentiometer / WFG --- ++ (+)a (+)b ---
thermocouple ++ ++ --- ++ (+)c
Current 0 to 20 mA --- ++ --- --- ---
Current 4 to 20 mA ++ ++ ++ ++ ++
voltage 0 to 10 V --- ++ --- --- ++
voltage 2 to 10 V ++ ++ ++ ++ ++
++ = is recognised  |  --- = is not recognised  |  (+) = is recognised conditionally
a is not recognised in all combinations
b A break in the measurement current path is not detected
c depending on the selected characteristic curve
Technical data – digital inputs
Parameter Description
input for volt-free contact Contact closed: input is active (RON < 1 kΩ)
Contact open: input inactive (ROFF > 50 kΩ)
sampling cycle 150 ms
Technical data – analogue output
Parameter Description
Voltage – output signal / load resistance DC 0(2) to 10 V
> 500 Ω
Current – output signal / load resistance DC 0(4) to 20 mA
< 450 Ω
Accuracy ≤ 0,5 %
influence of ambient temperature ≤ 150 ppm/K
Technical data – digital outputs
output type switching capacity / output signal Contact service life
relay (normally open contact) max. 3 A at 230 V AC or 30 V DC, resistive load 150,000 switching operations at rated load
350,000 switching operations at 1 A
relay (normally open contact) with extended contact life max. 3 A at 230 V AC, resistive load 300,000 switching operations at rated load
1,500,000 switching operations at 1 A
logic output DC 0/14 V ±15 %
max. 20 mA per output (at 14 V nominal voltage)
PhotoMOS®-Relaisa max. 200 mA at 30 V AC or 45 V DC;
not short-circuit proof
a PhotoMOS is a registered trademark of Panasonic Corporation.
Technical data – interfaces
interface Parameter value
USB-Device connector type Micro-B (socket)
Standard Low-Speed, Full-Speed
max. cable length 5 m
RS485 baud rate 9600, 19200, 38400, 115200
data format 8/1n, 8/1e, 8/1o, 8/2n
protocol Modbus RTU as slave
Ethernet connector type RJ45 (socket)
transmission rate 10 Mbit/s, 100 Mbit/s
protocol TCP/IP, DHCP;
Modbus-TCP, Modbus-RTU/ASCII over TCP, as Slave
Technical data – display (18-segment LCD)
Type Format Digit height of the upper display Digit height on the lower display
701510 132 7,2 mm 3,8 mm
701511 116 12,3 mm 5,9 mm
701512 108H 11,5 mm 8,5 mm
701513 108Q 16,5 mm 9 mm
701514 104 24,8 mm 12 mm
Additional technical data – display
Parameter Description
Color top display: white; bottom display: green
Figures including decimal places top display: 4;
lower display: 4 (5 for type 701510, 8 for type 701511)
decimal places 0, 1, 2, 3 or automatically (configurable)
Technical specifications – pixel-matrix LCD display (models 701512, 701513, 701514 only)
Type Format Pixel fields
701512 108H 2 Rows of 9 pixel fields each
701513 108Q 2 Rows of 8 pixel fields each
701514 104 2 Rows of 11 pixel fields each
Technical additional data – pixel-matrix LCD display
Parameter Value
Number of pixels per field 8 x 5
Color white
Technical specifications – Electrical specifications
Parameter Variant / Type Value
Power supply Variant 1 AC 110 to 240 V +10/-15 %, 48 to 63 Hz
Variant 2 (see the type plate) AC/DC 20 to 30 V, 48 to 63 Hz
Electrical safety in accordance with DIN EN 61010, Part 1;
Surge category II up to 300 V mains voltage, pollution degree 2
Protection class I with internal isolation to SELV
Power consumption Type 701510 (Format 132) at AC 110 to 240 V: max. 3,5 W
at AC/DC 20 to 30 V: max. 3,0 W
Type 701511 (Format 116) at AC 110 to 240 V: max. 4,1 W
at AC/DC 20 to 30 V: max. 3,7 W
Types 701512, 701513 (Formats 108H, 108Q) at AC 110 to 240 V: max. 5,8 W
at AC/DC 20 to 30 V: max. 5,7 W
Type 701514 (Format 104) at AC 110 to 240 V: max. 6,6 W
at AC/DC 20 to 30 V: max. 6,7 W
Electrical connection rear via spring-cage terminals (push-in technology)
Conductor cross-section solid or stranded wire (without ferrule) min. 0,2 mm², max. 1,5 mm²
stranded wire with ferrule without plastic collar: min. 0,2 mm², max. 1,5 mm²
with plastic collar: min. 0,2 mm², max. 0,75 mm²
Stripping length 8 mm
Technical data – environmental influences
Parameter Value / classification
Ambient temperature range
Storage -30 to +70 °C
Operation -10 to +55 °C
Installation height max. 2000 m AMSL (above mean sea level)
Climatic environmental conditions in accordance with DIN EN 60721-3, with an extended temperature range
climate resistance ≤ 90 % relative humidity without condensation
storage in accordance with class 1K2
Operation in accordance with class 3K3
Mechanical environmental conditions in accordance with DIN EN 60721-3
storage in accordance with class 1M2
Transport in accordance with class 2M2
Operation in accordance with class 3M3
Electromagnetic compatibility (EMC) in accordance with DIN EN 61326-1
Emitted interference Class A – for industrial use only –
Immunity to interference industrial requirement
Technical data – enclosure
Parameter Type / variant Value
Enclosure type Plastic enclosure for panel mounting in accordance with DIN IEC 61554 (indoor use)
Front panel made of plastic with membrane keypad
Panel thickness 1 to 10 mm
Enclosure mounting in the panel using the supplied mounting frame or the two mounting elements
Operating position anya
Ingress protection rating in accordance with DIN EN 60529, front IP65, rear IP20
Weight Type 701510 (Format 132) max. 85 g
Type 701511 (Format 116) max. 120 g
Type 701512 (Format 108H) max. 160 g
Type 701513 (Format 108Q) max. 160 g
Type 701514 (Format 104) max. 220 g
a The maximum permissible ambient temperature applies only when the display is installed in a vertical position.
Technical data – approvals and certification marks
Certification marks Test authority Certificates / approval numbers Test basis Applies to
c UL us Underwriters Laboratories E201387 UL 61010-1 (3. Ed.),
CAN/CSA-22.2 No. 61010-1 (3. Ed.)
all variants
DNV GL DNV GL TAA00001B3 Class Guideline DNVGL-CG-0339 Type 701511 (DC 20 bis 30 V)
and Type 701514 (AC 110 bis 240 V), without Ethernet interface, panel mounting
BUREAU VERITAS Bureau Veritas 53627/A0 BV Bureau Veritas Rules for the Classification of Steel Ships Type 701511 (DC 20 bis 30 V)
and Type 701514 (AC 110 bis 240 V), without Ethernet interface, panel mounting
The device is approved if the relevant certification mark is displayed on the device.