Product information "JUMO hydroTRANS S20 "

Humidity and temperature transmitter from JUMO with RS 485 Modbus output and integrated display

JUMO hydroTRANS S20 – Humidity and temperature transmitter with display (RS-485 Modbus) Type: 907042/11-0-15-530/994

With this version of the JUMO hydroTRANS S20, you receive a humidity and temperature transmitter for digital monitoring of indoor air quality with integrated RS-485 Modbus. It is particularly suitable for building automation, climate control, and industrial monitoring systems with additional local display.

The JUMO hydroTRANS S20 in this version is a combined transmitter for measuring relative humidity and temperature and is suitable for the continuous monitoring of ambient air in indoor areas as well as protected outdoor environments. Thanks to wall mounting, the device can be flexibly integrated into climate and building technology systems.

Technical data

  • Basic type extension: RH-T
  • Version: Standard
  • Measuring range: 0 … 100 % RH / -40 … +80 °C
  • Measured parameters: relative humidity, temperature
  • Output: RS-485 Modbus
  • Type addition: with integrated display

Advantages and technical features of the JUMO hydroTRANS S20

  • Digital communication via RS-485 Modbus
  • Integrated display for direct on-site reading
  • Combined measurement of humidity and temperature
  • Wide measuring range up to 100 % RH and -40 to +80 °C
  • Easy integration into building and automation systems
  • Robust design for continuous monitoring
  • Suitable for indoor areas and protected outdoor environments
  • Flexible wall mounting

This variant is additionally equipped with an integrated display, allowing the measured values to be read directly on the device. This simplifies local monitoring and reduces the need for additional readout devices during on-site inspections.

The combination of humidity and temperature sensor technology enables simultaneous acquisition of both measured variables. Optionally, a plastic sinter filter can be used to protect the sensor from dust and particles, thereby supporting the stability of the measured values in more demanding environments.

Typical areas of application

  • Building management and smart building systems
  • Ventilation and air conditioning systems
  • Indoor climate monitoring
  • Storage rooms and archives
  • Technical building equipment
  • Industrial environmental monitoring
  • Protected outdoor areas
Ordering details – JUMO hydroTRANS S20 Humidity and Temperature Transmitter
Pos. Feature Code Description
(1) Basic type 907042 JUMO hydroTRANS S20 – Humidity and Temperature Transmitter with optional CO2 module for wall mounting
(2) Basic type extension 11 RH – T
12 RH – T – CO2
(3) Version 0 Standard
(4) Measuring range 15 0 to 100 % RH / -40 to +80 °C
17 0 to 95 % RH / -10 to +60 °C / 10,000 ppm CO2
(5) Output 009 4 to 20 mA (factory setting) / 0 to 10 V combined output, configurable
530 RS485 Modbus
535 SPE with PoDL (Modbus TCP Slave) a
(6) Extra code 000 None
775 DAkkS (DKD) calibration (service), specify calibration points in plain text
994 Integrated display
Note a: Output 535 – SPE with PoDL (Modbus TCP Slave) is available only in combination with the CO2 module and an integrated display.
Ordering key – JUMO hydroTRANS S20
Designation (1) (2) (3) (4) (5) (6)
Ordering key   /   -   -   -   / , …a
Ordering example 907042 / 12 - 0 - 17 - 009 / 994
Note a: Multiple extra codes are listed consecutively and separated by commas.

Frequently Asked Questions

It measures humidity and temperature simultaneously.

For buildings, technical rooms, warehouses, and sheltered outdoor areas.

Yes, it is designed for continuous monitoring.

Yes, the integrated display shows temperature and humidity directly.

Yes, it can be easily integrated via RS-485 Modbus.

It is simply mounted on the wall.

No, the display shows the values directly on site.

Technical data:
Electrical safety
Requirements standard / specification
The device must be connected to a circuit that meets the requirements for “energy-limited circuits”. DIN EN IEC 61010-1:2020
Electrical specifications – device with analogue output
Power supply DC 24 V, -33 % / +33 %, SELV, PELV
power consumption ≤ 2,4 W
overvoltage category II
Degree of contamination 2
protection class DIN EN 61140, Class III (safety extra-low voltage)
electrical connection
connection elements spring-loaded terminal
connecting cable
  • cross-sectional area of the cable: AWG 28 to AWG 14
  • without ferrule: 0,2 bis 1,5 mm²
  • with ferrule: 0,25 bis 1,5 mm²
stripping length
  • without ferrule: 8 mm
  • with ferrule: 10 mm
temperature resistance ≥ 80 °C
Electrical data – device with RS485
power supply DC 24 V, -58 % / +33 %, SELV, PELV
power consumption ≤ 2,4 W
overvoltage category II
pollution degree 2
protection class DIN EN 61140, class III (safety extra-low voltage)
electrical connection
connection elements spring-cage terminal
connecting cable
  • cable cross-section: AWG 28 to AWG 14
  • without ferrule: 0,2 to 1,5 mm²
  • with ferrule: 0,25 to 1,5 mm²
stripping length
  • without ferrule: 8 mm
  • with ferrule: 10 mm
temperature resistance ≥ 80 °C
Electrical data – device with SPE
property value
supply voltage DC 18 to 30 V, PELV
current draw ≤ 100 mA
power consumption ≤ 1,8 W
overvoltage category II
pollution degree 2
protection class DIN EN 61140, class III (Ssafety extra-low voltage)
PoDL-class class 11, IEEE 802.3cg
PoDL classification SCCP- or Forced-Mode
electrical connection
connection element M12 connector
M12 connector IEC 63171-5
design 2-pin, shielded
ingress protection (IP rating) IP67
connecting cable IEC 61156-13, IEC 61156-14
cable design 2-core, copper, shielded
bandwidth ≥ 20 MHz
cable length ≤ 500 m (AWG22 at DC 24 V)
DC loop resistance < 59 Ω
temperature resistance ≥ 80 °C
Inputs – measured values – relative humidity
property value
measuring range
  • Standard: 0 to 100 % RH
  • with CO₂ module: 0 to 95 % RH
measurement accuracy
  • typical: ±2,0 % RH
  • max.: ±2,5 % RH
sampling rate 1 s
Inputs – temperature
Propertyt Value
measuring range
  • Standard: -40 to +80 °C
  • with CO₂ module: -10 to +60 °C
measurement accuracy
  • Typical: ±0,2 °C
  • Maximum: ±0,4 °C
sampling rate 1 s
Inputs – carbon dioxide (CO₂)
property Value
General information
Availability Optional for devices with an analogue output and RS485,
factory-set for devices with SPE
measurement range 400 to 10 000 ppm
measurement accuracy & reference conditions
measurement accuracy ±(50 ppm + 5 % of the measured value)
ambient temperature 25 °C
air pressure 1013 hPa
humidity 50 % RH
measuring range 400 to 1 000 ppm
sampling rate 30 s
Outputs – device with analogue output (current output signal)
property Value
current output
signal range 4 to 20 mA
output signal limits 0 to 22 mA
measurement accuracy ≤ ±0,05 % relative to the end of the signal range (20 mA)
temperature influence ±50 ppm/K
load influence ≤ ±0,02 % per 100 Ω
load ≤ 500 Ω
Outputs – voltage output
property Value
voltage output
signal range 0 to 10 V
output signal limits 0 to 11 V
accuracy ≤ ±0,05 % relative to the end of the signal range (10 V)
temperature influence 50 ppm/K
load influence ≤ ±15 mV
load ≥ 10 kΩ
Interfaces – USB
property specification
function transfer of configuration data and device information
communication via end device and setup software
transmission standard USB 2.0
connector type Micro-B
current consumption ≤ 500 mA
cable length ≤ 5 m
Interfaces – RS485
property specification
function Transfer of process data, configuration data and device information
communication via Modbus master
galvanic isolation functional
data transmission serial
transmission protocol Modbus RTU
data format
  • 8-1-nonea
  • 8-1-odd
  • 8-1-just
  • 8-2-none
a = factory setting
data transmission rate
  • 9600 Baud
  • 19200 Baud
  • 38400 Baud (factory setting)
  • 57600 Baud
  • 115200 Baud
minimum response time 0 to 500 ms
device address 1 to 254
Interfaces – SPE
property specification
function Transmission of process data, configuration data and device information, power supply via PoDL
communication Via the terminal and the JUMO Cloud, Modbus master
SPE standard 10BASE-T1L
transmission protocol Modbus TCP, integrated JUMO Cloud gateway
data transmission rate 10 Mbit/s
display
property specification
Type TFT-Display
Size Display Area: 35,04 mm × 28,03 mm
Screen diagonal: 1,77″
resolution 128 × 160 px RGB
brightness 11 Steps (configurable)
environmental influences
property specification
Permissible ambient temperature Permissible ambient temperature: -40 to +80 °C
With CO₂-Modul: -10 to +60 °C
With display: -20 to +60 °C
Permissible storage temperature Permissible storage temperature: -40 to +80 °C
With CO₂ module: -30 to +70 °C
With display unit: -30 to +60 °C
Degree of protection IP65 (DIN EN 60529)
Max. installation altitude 5300 m above sea level
Climatic conditions / climatic class DIN EN IEC 60721-3-3 / 3K24
Relative humidity ≤ 100 % (95 % with CO₂ module), non-condensing
Electromagnetic compatibility (EMC) DIN EN IEC 61326-2-3:2022
EMC – Emissions Class Ba
EMC – Immunity Industrial requirements
vibrationb vibration: DIN EN 60068-2-6
Deflection: 0,15 mm from 10 to 58,1 Hz
Acceleration: 20 m/s² from 58,1 to 150 Hz
Shockb Shock resistance according to DIN EN 60068-2-27
Peak acceleration: 150 m/s²
Shock duration: 11 ms
a The product is suitable for industrial use as well as for domestic and small business use.
b The CO₂ module is sensitive to vibrations. Due to its design, vibrations may affect the measurement result.
Mechanical properties
property specification
Materials of housing / display cover PC / PMMA
Weight Approx. 200 g