Product information "JUMO hydroTRANS S20 "
JUMO hydro TRANS S20 - Humidity and temperature transmitter with optional wall-mounted CO2 module
Typ: 907042/11-0-15-009/994
- Basic type extension: RH-T
- Version: Standard
- Measuring range: 0 ... 100 % rH / -40 ... +80°C
- Output: 4 ... 20 mA / 0 ... 10 V combi output config.
- Extra code: with integrated display
- Robustness
- Easy to install
- Multi-sensor
- Optional plastic sintered filter
The humidity and temperature transducer monitors the quality of the ambient air and can be wall-mounted both indoors and in protected outdoor areas.
Areas of application
- Climate monitoring
- Ventilation systems
- Building management
- Storage rooms
Other attributes
| Ausgang | 4...20 mA / 0...10 V (Kombiausgang konfiguriert) |
|---|---|
| Customs tariff number | 90258040 |
| Messbereich (Temperatur & relative Feuchte) | 0...100% rF / -40°C...+80°C |
| Messparameter | Relative Feuchte, Temperatur |
Downloads:
Electrical safety
|
Requirements |
DIN EN IEC 61010-1:2020 The device must be supplied with an electrical circuit that meets the requirements for "energy-limited circuits". |
Electric Dating
Device with analogue output
|
Power supply |
DC 24 V, -33 %/+33 %, SELV, PELV |
|
Power consumption |
≤ 2,4 W |
|
Surge Category |
II |
|
Degree |
2 |
|
Class |
DIN EN 61140, Class III (Protective extra-low voltage) |
|
Electrical connection Connection Elements |
Spring clamb |
|
Connection cable cable cable cross-section Without ferrule With ferrule Stripping length Without ferrule With ferrule Temperature resistance |
AWG 28 bis AWG 14 |
|
0,2 to 1,5 mm2 |
|
|
0,25 to 1,5 mm2 |
|
|
8 mm |
|
|
10 mm |
|
|
≥ 80 °C |
Device with RS485
|
Power supply |
DC 24 V, -58 %/+33 %, SELV, PELV |
|
Power consumption |
≤ 2,4 W |
|
Surge Category |
II |
|
Degree |
2 |
|
Class |
DIN EN 61140, Class III (Protective extra-low voltage) |
|
Electrical connection Connection Elements |
Spring clamb |
|
Connection cable cable cable cross-section Without ferrule With ferrule Stripping length Without ferrule With ferrule Temperature resistance |
AWG 28 to AWG 14 |
|
0,2 to 1,5 mm2 |
|
|
0,25 to 1,5 mm2 |
|
|
8 mm |
|
|
10 mm |
|
|
≥ 80 °C |
Device with SPE
|
Power supply |
DC 18 to 30 V, PELV |
|
Power consumption |
≤ 100 mA |
|
Power consumption |
≤ 1,8 W |
|
Surge Category |
II |
|
Degree |
2 |
|
Class |
DIN EN 61140, Class III (Protective extra-low voltage) |
|
PoDL-Class |
Class 11, IEEE 802.3cg |
|
PoDL-Classification |
SCCP- oder Forced-Mode |
|
Electrical connection Connector |
M12-Plug connection |
|
M12 Connectors |
IEC 63171-5 |
|
Execution |
2-polig, shielded |
|
Protection |
IP67 |
|
Trunk |
IEC 61156-13, IEC 61156-14 |
|
Execution |
2-adrig, Kupfer, shielded |
|
Bandwidth |
≥ 20 MHz |
|
Length |
≤ 500 m (AWG22 bei DC 24 V) |
|
DC Loop Resistor |
< 59 Ω |
|
Temperature resistance |
≥ 80 °C |
Inputs
Measuring range
Relative residual moisture
|
Measuring range With CO2 module |
0 to 100 % RH 0 to 95 % RH |
|
Accuracy |
|
|
Typical |
±2,0 % RH |
|
Max. |
±2,5 % RH |
|
Measurement Rate |
1 s |
Temperature
|
Measuring range With CO2 module |
-40 to +80 °C -10 to +60 °C |
|
Genauigkeit |
|
|
Typical |
±0,2 °C |
|
Max. |
±0,4 °C |
|
Measurement Rate |
1 s |
Carbon dioxide (CO2)
Optional on devices with analog output and RS485, factory on devices with SPE.
|
Measuring range |
400 to 10000 ppm |
|
Accuracy Reference Conditions Ambient temperature Air Pressure Humidity Measuring range |
±(50 ppm + 5 % from the measured value)
25 °C 1013 hPa 50 % RH 400 to 1 000 ppm |
|
Measurement Rate |
30 s |
Exits
Device with analogue output
Power Output
|
Signal Range |
4 to 20 mA |
|
Output Signal Limits |
0 to 22 mA |
|
Accuracy |
≤ ±0,05 % related to end of signal range (20 mA) |
|
Temperature |
±50 ppm/K |
|
Burden Influence |
≤ ±0,02 % pro 100 Ω |
|
Burde |
≤ 500 Ω |
Voltage output
|
Signal Range |
0 to 10 V |
|
Output Signal Limits |
0 to 11 V |
|
Accuracy |
≤ ±0,05 % related to end of signal range (10 V) |
|
Temperature |
50 ppm/K |
|
Load Influence |
≤ ±15 mV |
|
Last |
≥ 10 kΩ |
Interfaces
USB
|
Function |
Übertragen von Konfigurationsdaten und Geräteinformationen |
|
Communication |
Via device and setup software |
|
Transmission standard |
USB 2.0 |
|
Plug Type |
Micro-B |
|
Power |
≤ 500 mA |
|
Cable length |
≤ 5 m |
RS485
|
Function |
Übertragen von Prozessdaten, Konfigurationsdaten und Geräteinformationen |
|
Communication |
Über Modbus-Master |
|
Galvanic isolation |
Funktional |
|
Data transmission |
Seriell |
|
Transport |
Modbus RTU |
|
Data format |
8-1-nonea 8-1-odd 8-1-straight 8-2-none |
|
Data rate |
9600 Baud 19200 Baud 38400 Bauda 57600 Baud 115200 Baud |
|
Minimum response time |
0 to 500 ms |
|
Device Address |
1 to 254 |
a Default setting
SPE
|
Function |
Transmission of process data, configuration data and device information, power supply via PoDL |
|
Communication |
Via end device and JUMO Cloud, Modbus-Master |
|
SPE-Standard |
10BASE-T1L |
|
Transmission protocol |
Modbus TCP, Integrated JUMO Cloud-Gateway |
|
Data rate |
10 Mbit/s |
Display
|
Typ |
TFT-Display |
|
Size Display Screen diagonal |
35,04 mm × 28,03 mm 1,77″ |
|
Resolution |
128 × 160 px RGB |
|
Brightness |
11 Tiers (configurable)) |
Environmental impact
|
Permissible ambient temperature With CO2-Modul With Display |
-40 to +80 °C -10 to +60 °C -20 to +60 °C |
|
Permissible storage teperature With CO2- Modul With Display |
-40 to +80 °C -30 to +70 °C -30 to +60 °C |
|
Protection |
DIN EN 60529 IP65 |
|
Installation height max. |
5300 m above NN |
|
Climatic conditions Climat class Relative humidity |
DIN EN IEC 60721-3-3 3K24 ≤ 100 % (95 % with CO2-Modul), non-condensing |
|
Electromagnetic compatibility (EMC)) Emission Stability |
DIN EN IEC 61326-2-3:2022 Klasse Ba Industrieanforderung |
|
Vibration deflection Acceleration |
DIN EN 60068-2-6 0,15 mm from 10 to 58,1 Hz 20 m/s2 from 58,1 to 150 Hz |
|
Shockb Peak Acceleration Shock Duration |
DIN EN 60068-2-27 150 m/s2 11 ms |
a The product is suitable for industrial use as well as for household and small businesses.
b The CO2 module is sensitive to vibrations. In the event of vibrations, the measurement result may change due to the design.
Mechanical Properties
|
Materials Case Displaycover |
PC PMMA |
|
Weight |
Ca. 200 g |