JUMO outdoor resistance thermometers Protection class IP65

Article number: 802069
Our service hotline – We are here for you 📞 +49 (0) 5121 7609 99

Product information "JUMO outdoor resistance thermometers Protection class IP65 "

JUMO resistance thermometer for temperature measurements in indoor and outdoor areas as well as air ducts in the measuring range -50 to +90 °C

JUMO room, outdoor and duct resistance thermometer IP65 protection class Type: 902520/15-361-1003-1/000

The resistance thermometer with IP65 protection class is suitable for temperature measurements in indoor areas, outdoor environments and air ducts. This version is intended for measuring points that need to operate reliably not only indoors but also in more demanding environments. With a Pt100 in two-wire configuration, an operating range from -50 to +90 °C and IP65 protection class, this resistance thermometer is particularly suitable for HVAC applications where temperature must be measured in rooms, outdoor environments or air ducts.

Technical Data

  • Design: Room, outdoor and duct resistance thermometer
  • Measuring insert: 1 x Pt100
  • Circuit type: Two-wire configuration
  • Transmitter: none
  • Operating temperature: -50 to +90 °C
  • Protection class: IP65
  • Tolerance class: Class B

Advantages and technical features of the JUMO resistance thermometer

  • high IP65 protection class for more demanding environments
  • suitable for rooms, outdoor areas and air ducts
  • wide operating range from -50 to +90 °C
  • robust design for changing environmental conditions

The major advantage of this version lies in its higher protection class. IP65 makes it particularly suitable for installation locations where the housing needs better protection against dust and water jets. This makes it well suited for measuring points exposed to greater daily demands or technically more challenging environments than classic room sensors.

A Pt100 sensor in two-wire configuration is used for temperature measurement. This proven version is suitable for many common temperature measurement tasks in HVAC applications. Since no transmitter is integrated, this variant is especially useful where the sensor should be connected directly to a suitable control or evaluation unit.

The measuring range from -50 to +90 °C further extends the possible applications. This makes the version suitable not only for typical indoor temperatures but also for cooler or warmer environments as found in outdoor areas or air ducts.

Typical Areas of Application

  • room temperature measurement in HVAC applications
  • outdoor temperature measurement
  • temperature monitoring in air ducts
  • heating, ventilation and air conditioning systems

Dimensions

Height 5 cm
Length 19 cm
Width 18 cm

Weight

Weight 58 g

Other attributes

Country of origin DE
Customs tariff number 90251900
Messeinsatz 1x Pt 100 Zweileiterschaltung
Schutzart IP65
Temperaturbereich -50°C ... +90°C
Toleranz / Klasse Klasse B
Technical Data:
Technical Data
Feature Description
Connection housing Plastic housing made of PC (basic type 902520/11, material: PP), degree of protection IP20 to IP65.
Basic type 902524/25, degree of protection IP54 and IP65.
Protective tube Stainless steel 1.4571; Ø 6 mm
Measuring insert Pt100 temperature sensor, DIN EN 60751, class B, two-wire circuit.
Pt1000 temperature sensor, DIN EN 60751, class B, two-wire circuit.
Further versions, see ordering information.
Transmitter Analogue transmitter, output signal 4 to 20 mA or 0 to 10 V.
Transmitter
Characteristic Output 4 to 20 mA Output 0 to 10 V
Input
Measuring input Pt100 (DIN EN 60751) Pt100 (DIN EN 60751)
Sensor current ≤0,5 mA ≤0,5 mA
Measuring rate Continuous measurement, due to analogue signal path. Continuous measurement, due to analogue signal path.
Measuring circuit monitoring
Underrange (measuring range underrun) decreasing down to ≤ 3,6 mA 0 V
Overrange (measuring range overrun) rising to ≥ 22 up to < 28 mA
(typically 24 mA)
rising to ≥ 11 up to < 14 V
(typically 12 V)
Sensor short circuit ≤ 3,6 mA 0 V
Sensor and cable break ≥ 22 to < 28 mA (typically 24 mA) ≥ 11 to < 14 V (typically 12 V)
Output
Output signal Pulsed direct current 4 to 20 mA DC voltage 0 to 10 V
Transfer behaviour temperature-linear temperature-linear
Transmission accuracy ≤ ±0,1 % ≤ ±0,2 %
Attenuation of the residual ripple of a 24 V power supply, amplitude 10 V / 50 Hz, load 470 Ω / 10 MΩ load 37 dB 40 dB
Load (Rb) Rb = (Ub - 7,5 V) ÷ 22 mA -
Load effect ≤ ±0,02 % / 100 Ωa -
Load / Load Influence - ≥ 10 kΩ / ≤ ±0,1 %
Settling time after temperature change ≤ 10 ms ≤ 10 ms
Calibration conditions DC 24 V / approx. 22 °C DC 24 V / approx. 22 °C
Calibration accuracy ≤ ±0,2 %a,b or ≤ ±0,2 K ≤ ±0,2 %a,b or ≤ ±0,2 K
Overall sensor accuracy/Calibration ±0,4 K (typical) at 20 °C / 24 V
Power supply
±0,4 K (typical) at 20 °C / 24 V
Power supply
Power supply
Power supply (Ub) DC 7,5 at 30 V DC 15 at 30 V
Reverse polarity protection yes yes
Power supply influence ≤ ±0,01 %/V Deviation from 24 Va ≤ ±0,01 %/V Deviation from 24 Va
Environmental influences
Operating temperature range -40 to +85 °C -40 to +85 °C
Lagertemperaturbereich -40 to +100 °C -40 to +100 °C
Temperature influence ≤ ±0,01 %/K deviation from 22 °C a ≤ ±0,01 %/K deviation from 22 °C a
Climatic resistance
similar to DIN EN 60654 class C1
relative humidity ≤ 95% annual average without condensation relative humidity ≤ 95% annual average without condensation
EMC emissions and immunity EN 61326 class B, industrial requirements EN 61326 class B, industrial requirements

a All specifications refer to the full-scale value of 20 mA.
b The higher value applies.

Approvals / certifications
Certification marks Testing body Certificate / test number Basis for audit Applies to
SIL QUALIFIED
PL QUALIFIED
Type suffix 058
in conjunction with the manufacturer's declaration