Product information "JUMO room and outdoor RTD temperature probes Protection class IP54"
JUMO resistance thermometer for temperature measurements in indoor and outdoor areas with operating temperature range -20 to +80 °C
JUMO room and outdoor resistance thermometer without transmitter with IP54 protection class Type: 902520/11-635-1003-1/000
The resistance thermometer with IP54 protection class is suitable for temperature measurements in indoor and outdoor areas. With Pt100 in two-wire configuration and a measuring range from -20 to +80 °C, this version is designed for HVAC applications with increased protection requirements.
This version is intended for temperature measurements where the device should be better protected against environmental influences than standard room sensors. With a Pt100 in two-wire configuration, an operating range from -20 to +80 °C and IP54 protection class, this resistance thermometer is particularly suitable for HVAC applications where temperatures must be measured reliably indoors or outdoors.
Technical Data
- Design: Room and outdoor resistance thermometer
- Measuring insert: 1 x Pt100
- Circuit type: Two-wire configuration
- Transmitter: none
- Operating temperature: -20 to +80 °C
- Protection class: IP54
Advantages and technical features of the JUMO resistance thermometer for indoor and outdoor measurements
- suitable for indoor and outdoor areas
- IP54 protection class for better protected installation locations
- suitable for temperatures from -20 to +80 °C
- proven Pt100 for classic temperature measurement tasks
- direct integration without integrated transmitter
- good solution for HVAC applications with changing environmental conditions
- more robust design than standard indoor sensors
The main difference compared to simpler indoor variants is the more robust protection class. IP54 makes this version suitable for installation locations where dust or splash water may be present. This makes it well suited for applications where the sensor is used not only in protected indoor environments but also in more demanding surroundings.
A Pt100 sensor in two-wire configuration is used for temperature measurement. This is a proven solution for many classic measurement tasks in HVAC applications. Since no transmitter is integrated, this variant is especially suitable for applications where the sensor should be connected directly to compatible evaluation or control technology.
Typical Areas of Application
- room temperature measurement in HVAC applications
- outdoor temperature measurement on buildings
- technical indoor and outdoor environments
- heating, ventilation and air conditioning systems
- applications with increased protection requirements against dust and splash water
Dimensions
| Height | 6,5 cm |
|---|---|
| Length | 7,5 cm |
| Width | 7,5 cm |
Weight
| Weight | 43 g |
|---|
Other attributes
| Country of origin | RO |
|---|---|
| Customs tariff number | 90251900 |
| Messeinsatz | 1x Pt 100 Zweileiterschaltung |
| Schutzart | IP54 |
| Temperaturbereich | -20°C ... +80°C |
| Toleranz / Klasse | Klasse B |
| Feature | Description |
|---|---|
| Connection housing |
Plastic housing made of PC (basic type 902520/11, material: PP),
degree of protection IP20 to IP65. Basic type 902524/25, degree of protection IP54 and IP65. |
| Protective tube | Stainless steel 1.4571; Ø 6 mm |
| Measuring insert |
Pt100 temperature sensor, DIN EN 60751, class B, two-wire circuit. Pt1000 temperature sensor, DIN EN 60751, class B, two-wire circuit. Further versions, see ordering information. |
| Transmitter | Analogue transmitter, output signal 4 to 20 mA or 0 to 10 V. |
| Characteristic | Output 4 to 20 mA | Output 0 to 10 V |
|---|---|---|
| Input | ||
| Measuring input | Pt100 (DIN EN 60751) | Pt100 (DIN EN 60751) |
| Sensor current | ≤0,5 mA | ≤0,5 mA |
| Measuring rate | Continuous measurement, due to analogue signal path. | Continuous measurement, due to analogue signal path. |
| Measuring circuit monitoring | ||
| Underrange (measuring range underrun) | decreasing down to ≤ 3,6 mA | 0 V |
| Overrange (measuring range overrun) | rising to ≥ 22 up to < 28 mA (typically 24 mA) |
rising to ≥ 11 up to < 14 V (typically 12 V) |
| Sensor short circuit | ≤ 3,6 mA | 0 V |
| Sensor and cable break | ≥ 22 to < 28 mA (typically 24 mA) | ≥ 11 to < 14 V (typically 12 V) |
| Output | ||
| Output signal | Pulsed direct current 4 to 20 mA | DC voltage 0 to 10 V |
| Transfer behaviour | temperature-linear | temperature-linear |
| Transmission accuracy | ≤ ±0,1 % | ≤ ±0,2 % |
| Attenuation of the residual ripple of a 24 V power supply, amplitude 10 V / 50 Hz, load 470 Ω / 10 MΩ load | 37 dB | 40 dB |
| Load (Rb) | Rb = (Ub - 7,5 V) ÷ 22 mA | - |
| Load effect | ≤ ±0,02 % / 100 Ωa | - |
| Load / Load Influence | - | ≥ 10 kΩ / ≤ ±0,1 % |
| Settling time after temperature change | ≤ 10 ms | ≤ 10 ms |
| Calibration conditions | DC 24 V / approx. 22 °C | DC 24 V / approx. 22 °C |
| Calibration accuracy | ≤ ±0,2 %a,b or ≤ ±0,2 K | ≤ ±0,2 %a,b or ≤ ±0,2 K |
| Overall sensor accuracy/Calibration | ±0,4 K (typical) at 20 °C / 24 V Power supply |
±0,4 K (typical) at 20 °C / 24 V Power supply |
| Power supply | ||
| Power supply (Ub) | DC 7,5 at 30 V | DC 15 at 30 V |
| Reverse polarity protection | yes | yes |
| Power supply influence | ≤ ±0,01 %/V Deviation from 24 Va | ≤ ±0,01 %/V Deviation from 24 Va |
| Environmental influences | ||
| Operating temperature range | -40 to +85 °C | -40 to +85 °C |
| Lagertemperaturbereich | -40 to +100 °C | -40 to +100 °C |
| Temperature influence | ≤ ±0,01 %/K deviation from 22 °C a | ≤ ±0,01 %/K deviation from 22 °C a |
| Climatic resistance similar to DIN EN 60654 class C1 |
relative humidity ≤ 95% annual average without condensation | relative humidity ≤ 95% annual average without condensation |
| EMC emissions and immunity | EN 61326 class B, industrial requirements | EN 61326 class B, industrial requirements |
a All specifications refer to the full-scale value of 20 mA.
b The higher value applies.
| Certification marks | Testing body | Certificate / test number | Basis for audit | Applies to |
|---|---|---|---|---|
|
SIL QUALIFIED PL QUALIFIED |
– | – | – |
Type suffix 058 in conjunction with the manufacturer's declaration |