Wall-Mounted Resistance Thermometer with Pt1000 in Two-Wire Circuit and Operating Temperature -30 to +90 °C

JUMO Wall-Mounted Resistance Thermometer with Remote Protection Tube Protection Class IP65 Type: 902520/23-573-1005-1/000

The wall-mounted resistance thermometer is suitable for HVAC temperature measurements with a spatially separated measuring point. Equipped with Pt1000 in a two-wire circuit, a measuring range of -30 to +90 °C, a remote protection tube, and protection class IP65, this version is designed for wall-mounted measuring points where the actual measuring location is not directly inside the housing but is detected via a remote protection tube. It is particularly suitable for HVAC applications in indoor and protected outdoor areas.

Technical Data

  • Version: Wall-mounted resistance thermometer with remote protection tube
  • Measuring insert: 1 x Pt1000
  • Circuit type: Two-wire circuit
  • Transmitter: without
  • Operating temperature: -30 to +90 °C
  • Protection class: IP65

Advantages and Technical Features of the JUMO Wall-Mounted Resistance Thermometer

  • remote protection tube for more targeted temperature measurement
  • Pt1000 sensor for compatible control and evaluation systems
  • IP65 protection class for increased housing protection requirements
  • well suited for wall-mounted measuring points with a spatially separated measuring location

The remote protection tube makes this version especially useful where the temperature should not be measured directly at the wall surface but with some distance from it. This allows the sensor to be positioned more precisely at the relevant measuring point while the housing remains mounted separately. This is particularly practical when the measuring point is structurally not located directly at the installation position of the housing.

Unlike Pt100 versions, this model operates with 1 x Pt1000 in a two-wire circuit. This is especially beneficial when the connected control or evaluation system is designed for Pt1000 or when this sensor configuration is preferred. Since no transmitter is integrated, the device is particularly suitable for applications where the sensor should be connected directly to a compatible evaluation unit.

With protection class IP65, the housing is well protected against dust and water. This makes the version suitable for environments where a more robust wall-mounted solution is required than standard room sensors. Especially in technically demanding HVAC environments, this is a clear advantage.

Typical Applications

  • Wall-mounted measuring points in HVAC applications
  • Temperature monitoring with a slightly remote measuring point
  • Heating, ventilation, and air conditioning systems
  • Technical indoor areas
  • Protected outdoor areas

Dimensions

Height 7 cm
Length 5,2 cm
Width 10 cm

Weight

Weight 90 g

Other attributes

Country of origin DE
Customs tariff number 90251900
Messeinsatz 1x Pt 1000 Zweileiterschaltung
Temperaturbereich -30°C ... +90°C
Toleranz / Klasse Klasse B
Technical Data:
Technical Data
Feature Description
Connection housing Plastic housing made of PC (basic type 902520/11, material: PP), degree of protection IP20 to IP65.
Basic type 902524/25, degree of protection IP54 and IP65.
Protective tube Stainless steel 1.4571; Ø 6 mm
Measuring insert Pt100 temperature sensor, DIN EN 60751, class B, two-wire circuit.
Pt1000 temperature sensor, DIN EN 60751, class B, two-wire circuit.
Further versions, see ordering information.
Transmitter Analogue transmitter, output signal 4 to 20 mA or 0 to 10 V.
Transmitter
Characteristic Output 4 to 20 mA Output 0 to 10 V
Input
Measuring input Pt100 (DIN EN 60751) Pt100 (DIN EN 60751)
Sensor current ≤0,5 mA ≤0,5 mA
Measuring rate Continuous measurement, due to analogue signal path. Continuous measurement, due to analogue signal path.
Measuring circuit monitoring
Underrange (measuring range underrun) decreasing down to ≤ 3,6 mA 0 V
Overrange (measuring range overrun) rising to ≥ 22 up to < 28 mA
(typically 24 mA)
rising to ≥ 11 up to < 14 V
(typically 12 V)
Sensor short circuit ≤ 3,6 mA 0 V
Sensor and cable break ≥ 22 to < 28 mA (typically 24 mA) ≥ 11 to < 14 V (typically 12 V)
Output
Output signal Pulsed direct current 4 to 20 mA DC voltage 0 to 10 V
Transfer behaviour temperature-linear temperature-linear
Transmission accuracy ≤ ±0,1 % ≤ ±0,2 %
Attenuation of the residual ripple of a 24 V power supply, amplitude 10 V / 50 Hz, load 470 Ω / 10 MΩ load 37 dB 40 dB
Load (Rb) Rb = (Ub - 7,5 V) ÷ 22 mA -
Load effect ≤ ±0,02 % / 100 Ωa -
Load / Load Influence - ≥ 10 kΩ / ≤ ±0,1 %
Settling time after temperature change ≤ 10 ms ≤ 10 ms
Calibration conditions DC 24 V / approx. 22 °C DC 24 V / approx. 22 °C
Calibration accuracy ≤ ±0,2 %a,b or ≤ ±0,2 K ≤ ±0,2 %a,b or ≤ ±0,2 K
Overall sensor accuracy/Calibration ±0,4 K (typical) at 20 °C / 24 V
Power supply
±0,4 K (typical) at 20 °C / 24 V
Power supply
Power supply
Power supply (Ub) DC 7,5 at 30 V DC 15 at 30 V
Reverse polarity protection yes yes
Power supply influence ≤ ±0,01 %/V Deviation from 24 Va ≤ ±0,01 %/V Deviation from 24 Va
Environmental influences
Operating temperature range -40 to +85 °C -40 to +85 °C
Lagertemperaturbereich -40 to +100 °C -40 to +100 °C
Temperature influence ≤ ±0,01 %/K deviation from 22 °C a ≤ ±0,01 %/K deviation from 22 °C a
Climatic resistance
similar to DIN EN 60654 class C1
relative humidity ≤ 95% annual average without condensation relative humidity ≤ 95% annual average without condensation
EMC emissions and immunity EN 61326 class B, industrial requirements EN 61326 class B, industrial requirements

a All specifications refer to the full-scale value of 20 mA.
b The higher value applies.

Approvals / certifications
Certification marks Testing body Certificate / test number Basis for audit Applies to
SIL QUALIFIED
PL QUALIFIED
Type suffix 058
in conjunction with the manufacturer's declaration