Product information "JUMO wall resistance thermometer with remote protection tube Protection class IP65 "

Wall-Mounted Resistance Thermometer by JUMO with Pt100 and Integrated Transmitter with 4–20 mA and Measuring Range -40 to +80 °C

JUMO Wall-Mounted Resistance Thermometer with Remote Protection Tube Protection Class IP65 Type: 902520/23-474-1003-1/330,(-40..80°C)

The wall-mounted resistance thermometer is suitable for HVAC temperature measurements with direct analog signal transmission. Equipped with Pt100 in a two-wire circuit, an integrated 4 to 20 mA transmitter, and a measuring range of -40 to +80 °C, this version is particularly suitable for robust wall-mounted measuring points with a separated measuring location.

This version is designed for wall-mounted measuring points where the temperature value should be recorded at a location slightly removed from the housing and transmitted directly as a current signal. For this purpose, the version is equipped with a remote protection tube.

Technical Data

  • Version: Wall-mounted resistance thermometer with remote protection tube
  • Measuring insert: 1 x Pt100
  • Circuit type: Two-wire circuit
  • Transmitter: 1 x analog, output 4 to 20 mA
  • Measuring range: -40 to +80 °C
  • Note: Measuring range only in combination with transmitter
  • Protection class: IP65

Advantages and Technical Features of this Wall-Mounted Resistance Thermometer

  • remote protection tube for more targeted temperature measurement
  • well suited for wall-mounted measuring points with a separated measuring location
  • no additional external signal conversion required
  • suitable for applications with an extended temperature range up to +80 °C

The remote protection tube offers a clear advantage: the sensor can be positioned closer to the actual measuring point while the housing remains mounted separately on the wall. This is practical wherever temperature values should not be measured directly at the housing position but require a small distance from the actual measuring location.

In addition, the integrated 4 to 20 mA transmitter provides the temperature signal immediately as a common analog output signal and allows direct connection to suitable controllers or control systems. Especially in building automation and HVAC applications, this is useful when no additional external signal conversion is planned. The associated measuring range is -40 to +80 °C and applies to this version in combination with the transmitter.

The housing design is also intended for more demanding installation environments. With protection class IP65, the device is well protected against dust and water. This makes the version particularly suitable for wall-mounted measuring points in technically demanding indoor areas or protected outdoor areas.

Typical Applications

  • Wall-mounted measuring points in HVAC applications
  • Building automation
  • Heating, ventilation, and air conditioning systems
  • Measuring points with a slightly remote measuring location
  • Technical indoor areas and protected outdoor areas

Dimensions

Height 7 cm
Length 5,2 cm
Width 10 cm

Weight

Weight 93 g

Other attributes

Country of origin DE
Customs tariff number 90251900
Messeinsatz 1x Pt 100 Zweileiterschaltung
Messumformer Messumformer analog Ausgang 4-20 mA
Temperaturbereich -40°C ... +80°C
Toleranz / Klasse Klasse B
Technical Data:
Technical Data
Feature Description
Connection housing Plastic housing made of PC (basic type 902520/11, material: PP), degree of protection IP20 to IP65.
Basic type 902524/25, degree of protection IP54 and IP65.
Protective tube Stainless steel 1.4571; Ø 6 mm
Measuring insert Pt100 temperature sensor, DIN EN 60751, class B, two-wire circuit.
Pt1000 temperature sensor, DIN EN 60751, class B, two-wire circuit.
Further versions, see ordering information.
Transmitter Analogue transmitter, output signal 4 to 20 mA or 0 to 10 V.
Transmitter
Characteristic Output 4 to 20 mA Output 0 to 10 V
Input
Measuring input Pt100 (DIN EN 60751) Pt100 (DIN EN 60751)
Sensor current ≤0,5 mA ≤0,5 mA
Measuring rate Continuous measurement, due to analogue signal path. Continuous measurement, due to analogue signal path.
Measuring circuit monitoring
Underrange (measuring range underrun) decreasing down to ≤ 3,6 mA 0 V
Overrange (measuring range overrun) rising to ≥ 22 up to < 28 mA
(typically 24 mA)
rising to ≥ 11 up to < 14 V
(typically 12 V)
Sensor short circuit ≤ 3,6 mA 0 V
Sensor and cable break ≥ 22 to < 28 mA (typically 24 mA) ≥ 11 to < 14 V (typically 12 V)
Output
Output signal Pulsed direct current 4 to 20 mA DC voltage 0 to 10 V
Transfer behaviour temperature-linear temperature-linear
Transmission accuracy ≤ ±0,1 % ≤ ±0,2 %
Attenuation of the residual ripple of a 24 V power supply, amplitude 10 V / 50 Hz, load 470 Ω / 10 MΩ load 37 dB 40 dB
Load (Rb) Rb = (Ub - 7,5 V) ÷ 22 mA -
Load effect ≤ ±0,02 % / 100 Ωa -
Load / Load Influence - ≥ 10 kΩ / ≤ ±0,1 %
Settling time after temperature change ≤ 10 ms ≤ 10 ms
Calibration conditions DC 24 V / approx. 22 °C DC 24 V / approx. 22 °C
Calibration accuracy ≤ ±0,2 %a,b or ≤ ±0,2 K ≤ ±0,2 %a,b or ≤ ±0,2 K
Overall sensor accuracy/Calibration ±0,4 K (typical) at 20 °C / 24 V
Power supply
±0,4 K (typical) at 20 °C / 24 V
Power supply
Power supply
Power supply (Ub) DC 7,5 at 30 V DC 15 at 30 V
Reverse polarity protection yes yes
Power supply influence ≤ ±0,01 %/V Deviation from 24 Va ≤ ±0,01 %/V Deviation from 24 Va
Environmental influences
Operating temperature range -40 to +85 °C -40 to +85 °C
Lagertemperaturbereich -40 to +100 °C -40 to +100 °C
Temperature influence ≤ ±0,01 %/K deviation from 22 °C a ≤ ±0,01 %/K deviation from 22 °C a
Climatic resistance
similar to DIN EN 60654 class C1
relative humidity ≤ 95% annual average without condensation relative humidity ≤ 95% annual average without condensation
EMC emissions and immunity EN 61326 class B, industrial requirements EN 61326 class B, industrial requirements

a All specifications refer to the full-scale value of 20 mA.
b The higher value applies.

Approvals / certifications
Certification marks Testing body Certificate / test number Basis for audit Applies to
SIL QUALIFIED
PL QUALIFIED
Type suffix 058
in conjunction with the manufacturer's declaration