JUMO room resistance thermometers Protection class IP20
€99.72*
Please log in to receive your conditions.
Available in 28 days, delivery time 1-2 days
(Login for quotation) The entered number of pieces will be taken into account when creating the quotation.
Product information "JUMO room resistance thermometers Protection class IP20"
JUMO room resistance thermometer for temperature measurement in indoor areas and HVAC applications for measuring range -30 to +80 °C
JUMO room resistance thermometer with Pt100 in three-wire configuration and IP20 protection class Type: 902520/10-572-1001-1/00
The room resistance thermometer with IP20 protection class is designed for temperature measurement in indoor areas and HVAC applications. With Pt100 in three-wire configuration and a measuring range from -30 to +80 °C, this version is suitable for reliable room temperature detection.
This room resistance thermometer is designed for temperature measurement in indoor environments and is particularly suitable for HVAC applications. With a Pt100 temperature sensor in three-wire configuration and an operating range from -30 to +80 °C, this version is designed for reliable temperature detection in typical room-related applications.
Technical Data
- Design: Room resistance thermometer
- Measuring insert: 1 x Pt100
- Circuit type: Three-wire configuration
- Transmitter: none
- Operating temperature: -30 to +80 °C
- Protection class: IP20
Advantages and technical features
- suitable for classic room temperature measurements
- well suited for HVAC applications
- three-wire configuration for more accurate temperature measurement
- suitable for temperatures from -30 to +80 °C
Its strengths are especially apparent wherever temperatures in rooms need to be continuously monitored without requiring a complex sensor design. The IP20 protection class makes this version suitable for dry indoor areas where the sensor is primarily used for room temperature detection. This makes the device well suited for classic building services and HVAC applications.
The integrated Pt100 sensor belongs to the proven solutions in temperature measurement technology. In this version, it is designed as a three-wire configuration, which is particularly advantageous when cable influences should be compensated better than with a simple two-wire configuration. This supports the most precise and stable temperature measurement possible during operation.
Since no transmitter is integrated, this version is particularly suitable for applications where the sensor should be connected directly to compatible evaluation or control technology. This can be useful wherever simple and direct integration into existing systems is required.
Typical Areas of Application
- room temperature measurement in HVAC applications
- temperature monitoring in indoor environments
- building services engineering
- ventilation and air conditioning systems
- dry indoor areas with low mechanical stress
Frequently Asked Questions
It reliably measures temperature in indoor spaces and HVAC systems.
Depending on the specific model, the measuring range is −30 °C to +80 °C, 0 °C to +40 °C, or 0 °C to +60 °C.
Yes, it is specifically designed for air conditioning and ventilation applications.
In dry indoor areas such as offices, plant rooms, and general building interiors.
It connects directly to compatible evaluation or control equipment.
As standard, it uses a Pt100 temperature sensor compliant with DIN EN 60751.
It has an IP20 protection rating (protection against solid foreign objects, but not against water).
Dimensions
| Height | 3 cm |
|---|---|
| Length | 12 cm |
| Width | 8 cm |
Weight
| Weight | 50 g |
|---|
Other attributes
| Country of origin | DE |
|---|---|
| Customs tariff number | 90251900 |
| Messeinsatz | 1x Pt 100 Dreileiterschaltung |
| Schutzart | IP20 |
| Temperaturbereich | -30°C ... +80°C |
| Toleranz / Klasse | Klasse B |
| Feature | Description |
|---|---|
| Connection housing |
Plastic housing made of PC (basic type 902520/11, material: PP),
degree of protection IP20 to IP65. Basic type 902524/25, degree of protection IP54 and IP65. |
| Protective tube | Stainless steel 1.4571; Ø 6 mm |
| Measuring insert |
Pt100 temperature sensor, DIN EN 60751, class B, two-wire circuit. Pt1000 temperature sensor, DIN EN 60751, class B, two-wire circuit. Further versions, see ordering information. |
| Transmitter | Analogue transmitter, output signal 4 to 20 mA or 0 to 10 V. |
| Characteristic | Output 4 to 20 mA | Output 0 to 10 V |
|---|---|---|
| Input | ||
| Measuring input | Pt100 (DIN EN 60751) | Pt100 (DIN EN 60751) |
| Sensor current | ≤0,5 mA | ≤0,5 mA |
| Measuring rate | Continuous measurement, due to analogue signal path. | Continuous measurement, due to analogue signal path. |
| Measuring circuit monitoring | ||
| Underrange (measuring range underrun) | decreasing down to ≤ 3,6 mA | 0 V |
| Overrange (measuring range overrun) | rising to ≥ 22 up to < 28 mA (typically 24 mA) |
rising to ≥ 11 up to < 14 V (typically 12 V) |
| Sensor short circuit | ≤ 3,6 mA | 0 V |
| Sensor and cable break | ≥ 22 to < 28 mA (typically 24 mA) | ≥ 11 to < 14 V (typically 12 V) |
| Output | ||
| Output signal | Pulsed direct current 4 to 20 mA | DC voltage 0 to 10 V |
| Transfer behaviour | temperature-linear | temperature-linear |
| Transmission accuracy | ≤ ±0,1 % | ≤ ±0,2 % |
| Attenuation of the residual ripple of a 24 V power supply, amplitude 10 V / 50 Hz, load 470 Ω / 10 MΩ load | 37 dB | 40 dB |
| Load (Rb) | Rb = (Ub - 7,5 V) ÷ 22 mA | - |
| Load effect | ≤ ±0,02 % / 100 Ωa | - |
| Load / Load Influence | - | ≥ 10 kΩ / ≤ ±0,1 % |
| Settling time after temperature change | ≤ 10 ms | ≤ 10 ms |
| Calibration conditions | DC 24 V / approx. 22 °C | DC 24 V / approx. 22 °C |
| Calibration accuracy | ≤ ±0,2 %a,b or ≤ ±0,2 K | ≤ ±0,2 %a,b or ≤ ±0,2 K |
| Overall sensor accuracy/Calibration | ±0,4 K (typical) at 20 °C / 24 V Power supply |
±0,4 K (typical) at 20 °C / 24 V Power supply |
| Power supply | ||
| Power supply (Ub) | DC 7,5 at 30 V | DC 15 at 30 V |
| Reverse polarity protection | yes | yes |
| Power supply influence | ≤ ±0,01 %/V Deviation from 24 Va | ≤ ±0,01 %/V Deviation from 24 Va |
| Environmental influences | ||
| Operating temperature range | -40 to +85 °C | -40 to +85 °C |
| Lagertemperaturbereich | -40 to +100 °C | -40 to +100 °C |
| Temperature influence | ≤ ±0,01 %/K deviation from 22 °C a | ≤ ±0,01 %/K deviation from 22 °C a |
| Climatic resistance similar to DIN EN 60654 class C1 |
relative humidity ≤ 95% annual average without condensation | relative humidity ≤ 95% annual average without condensation |
| EMC emissions and immunity | EN 61326 class B, industrial requirements | EN 61326 class B, industrial requirements |
a All specifications refer to the full-scale value of 20 mA.
b The higher value applies.
| Certification marks | Testing body | Certificate / test number | Basis for audit | Applies to |
|---|---|---|---|---|
|
SIL QUALIFIED PL QUALIFIED |
– | – | – |
Type suffix 058 in conjunction with the manufacturer's declaration |